The heater gas inlet connection is 3/8" NPT at the regula-
tor, inlet on the right side facing the gas log. If a left side
connection is required, the connecting pipe may be led
under the rear of the gas logs or behind the grate for con-
nection to the inlet.
NOTE: The millivolt valve has an internal regulator, thus
the incoming gas line connects directly to the valve.
Test all gas joints from the gas meter to the appliance
regulator for leaks using a gas analyzer or soap and water
solution after completing connection. DO NOT USE AN
OPEN FLAME.
Check the gas pressure with the appliance burning.
MANUAL CONTROL
Figure 6
The pressure regulator is preset and locked to discourage
tampering. If the pressure is not as specified, replace with
the correct part from the parts list in this manual.
Remove 1/8" NPT plug, located on side of regulator body.
Install fitting and tubing to pressure gauge. After tak-
ing pressure reading, re-install test plug. Check for gas
leaks.
NPT Test Plug
Figure 6 -
Manual Control Pressure
Test Point Location
FP2499
manual valve
8

MILLIVOLT CONTROL

Figure 7
The valve regulator controls the burner pressure which
should be checked at the pressure test point. Turn captured
screw counter clockwise 2 or 3 turns and then place tubing
to pressure gauge over test point (Use test point labeled
"OUT"). After taking pressure reading, be sure and turn
captured screw clockwise firmly to re-seal. Do not over
torque. Check for gas leaks.
Figure 7 -
Pressure Test Point Location
FP2499
GAS LINE CONNECTION
Test Port "Out"
FP2856

millivolt valve

FP2856
32D1999