Appendix: Ups Installation Guide - Liebert GHT MT+ User Manual

Single phase online ups 1000-3000 va
Table of Contents

Advertisement

UPS should be placed on the flat and clean surface. Place it in an area away from
1.
vibration, dust, humidity, high temperature, flammable liquids, gases, corrosive and
conductive contaminants. Install the UPS indoors in a clean environment, where it is
away from window and door. Maintain minimum clearance of 100mm in the bottom of
the UPS to avoid dust and high temperature.
Maintain an ambient temperature range of 0ºC to 45ºC for UPS optimal operation. For
2.
every 5ºC above 45ºC, the UPS will derate 12% of nominal capacity at full load. The
highest working temperature requirement for UPS operation is 50ºC.
It's required to maintain maximum altitude of 1000m to keep UPS normal operation at
3.
full load UPS. If it's used in high altitude area, please reduce connected load. Altitude
derating power with connected loads for UPS normal operation is listed as below:
Use supplied RS-232 or USB communication cable to connect RS-232/USB port of UPS
4.
and RS-232/USB port of PC. After installing ViewPower in PC, it can remote monitor
UPS.

Appendix: UPS Installation Guide