Installation; Preparation; Tower Ups Installation - Liebert GXT2U User Manual

120v, 500-3000va
Hide thumbs Also See for GXT2U:
Table of Contents

Advertisement

4.0
I
NSTALLATION
4.1
P
REPARATION
1. Visually inspect the UPS for freight damage. Report damage to
the carrier and your local dealer or Liebert representative.
CAUTION
!
The UPS is heavy (see 11.0 - Specifications). Take proper
precautions when lifting or moving it.
2. Decide where to place the Liebert GXT2U. Install the UPS indoors
in a controlled environment, where it cannot be accidentally
turned off. Place it in an area of unrestricted airflow around the
unit, away from water, flammable liquids, gases, corrosives, and
conductive contaminants. Maintain a minimum clearance of 4 in.
(100mm) in the front and rear of the UPS. Maintain an ambient
temperature range of 32°F to 104°F (0°C to 40°C).
NOTE
UPS operation in temperatures above 77°F (25°C) reduces
battery life.
3. The Liebert GXT2U may be installed in either a tower
configuration or in a rack, depending on available space and use
considerations. Determine the type of installation and follow the
appropriate instructions in either 4.2 - Tower UPS Installation
or 4.3 - Rack-Mount UPS Conversion and Installation.
4.2
T
OWER
When using the Liebert GXT2U in a tower configuration, use the
included support base (shown below, left) to stabilize the UPS.
If any battery cabinets are added, they will include spacers to accom-
modate the additional cabinets (shown below, right).
Support base
UPS I
NSTALLATION
Spacers added to support
base to accommodate
additional battery cabinets
8

Installation