Sharing Peak Power Control Information with other DMS'

 By sharing the peak power control information with other DMS' ,
several buildings can be controlled using the peak power control.
 This setting consists of one master DMS and several slave DMS'
and the information of the master DMS must be set on all slave
DMS' . The default DMS setting is set to master.
Demand Controller
Power Cable
Communication,
point of contact
 Master DMS transmits the received Peak Level periodically to
the connected slave DMS' and the slave DMS performs demand
control according to the received Peak Level.
The master/slave setting can be set through the Web and the DMS
with the peak interface module connected must be set to be master.
MIM-Doo_IB_E_25059.indd
11
Power board
Peak I/M
Master
DMS
Sharing of Peak Level
Building A
Slave DMS
Building B
Slave DMS
Building C
Slave DMS
2006-03-21