2) Operation Mode
 Peak power control runs in one of the 3 modes:
'No Control', 'Priority Control Mode' , and 'Circulation Control Mode. '
 No Control:
If the peak power control mode is set to 'No Control' , peak power control will not run.
The default DMS setting is set to 'No Control' mode.
 Priority Control Mode:
In Priority Control Mode, priorities are set for each indoor unit and the indoor units are
controlled according to the priorities set when the peak level is received.
 The operation is as follow:
Input Peak
Level
Level 0
Level 1
Level 2
Level 3
 The priority of each indoor unit can be set through the Web or using the upper level
controller of the DMS.
 Circulation Control Mode:
In Circulation Control Mode, indoor units are classified into several groups and each group or
groups are controlled by the peak power function periodically.
 The operation is as follow:
Input Peak
Level
Level 0
Level 1
Level 2
Level 3
 A group or a groups of indoor units are controlled by the peak power function for a set
period of time and the following group or groups are controlled after the set period of
time and so on. The group or groups of indoor units released from peak power function
restore their operation status to before being controlled by the peak power function.
7
Group
6
5
Input Peak Level : 0 1
MIM-Doo_IB_E_25059.indd
9
Peak Power Control Applied Group
Peak power control not performed.
Only groups with priority set to 1 receive peak control.
Only groups with priority set to 1 and 2 receive peak control.
Only groups with priorities set to 1, 2, and 3 receive peak control.
Peak Power Control Applied Group
Peak power control not performed.
1 group circulation control (Peak control for only 1 group)
2 groups circulation control (Peak control for only 2 groups)
3 groups circulation control (Peak control for only 3 groups)
1
7
2
6
3
5
4
Input Peak Level : 0 1
1
7
2
Group
6
3
5
4
Input Peak Level : 0 1
1
2
Group
3
4
9
E-
2006-03-21