FREESTANDING COMBUSTIBLE SURFACE CLEARANCE DIMENSIONS (I
Installation type
No Heat Shield &
single wall connector
No Heat Shield &
double wall connector
Rear Heat Shield &
single wall connector
Rear Heat Shield &
double wall connector
* Measured from the body of the stove, not the heat shield. ** A and E apply to the side of stove where the side door is installed.
ALCOVE COMBUSTIBLE SURFACE CLEARANCE DIMENSIONS (I
Installation type
No Heat Shield & single wall connector
Rear Heat Shield & single wall connector
Rear Heat Shield & double wall connector
If you use a rear heat shield to obtain reduced
clearances, you must only use the optional rear heat
shield manufactured by Hearthstone specifically for
the Equinox Model 8000 (Heat Shield part number:
90-68000) , which is available through your local
dealer.
Use only close clearance connector pipe tested to
UL standards and listed. Check listings of your pipe
HearthStone Quality Home Heating Products, Inc ®
Figure 4: Fireplace Installation Clearances
Parallel
A**
B
C
21
21
22-3/4
26-3/4
20
17
18-3/4
22-3/4
22
8 *
9-3/4
13-3/4
19
6 *
7-3/4
11-3/4
D
E**
F
37-1/4
18-1/4
36-1/4
14-1/4
38-1/4
5-1/4
35-1/4
3-1/4
A**
20
21
20
for actual clearances. Measurements shown above
and on the following page are specific to the
Simpson Dura Vent DVL brand. Do not reduce
clearances without the use of the rear heat shield
and/or with close clearance connector pipe and/or
by protecting the combustible surfaces per NFPA
211 standards. See NFPA-211 for protected
surface clearance requirements.
10
) (US
NCHES
REQUIREMENTS
Corner
G
H
I
59-3/4
15
26-3/8
55-3/4
14-1/2
25-7/8
46-3/4
15-1/2
26-7/8
44-3/4
13-1/2
24-7/8
)
NCHES
B
Top of Stove to Ceiling
21
8
6
)
J
K
30-3/8
76
29-7/8
75-1/3
30-7/8
76-3/4
28-7/8
73-7/8
67
67
67
Equinox Model 8000