FDC-HKXR
Current cut is indicated and the compressor cannot operate
Disconnect the compressor wiring
The compressor can operate
Is the current
cut function activated?
NO
Is the output
voltage of the inverter
normal?
YES
When the compressor wiring is
performed, the unit can operate.
Isn't the stating
current
(2)
excessive?
NO
Defective inverter
1082
Is the insullaiton
resistance of the compressor
proper?
YES
YES
Defective inverter
(Refer to 1090 page)
NO
Defective inverter
(Refer to 1090 page)
YES
Defective compressor
Inverter output voltage
Frequency
35 Hz
Model
All models
95 ~ 98
(outdoor unit)
NO
Defective compressor
(1)
Notes (1) When a short-circuit or ground-fault occurs
in the compressor motor, the current cut
function is also activated.
Notes (1)
If the insulation resistance is 10MΩ or more,
it is normal.
Notes (1)
The insulation resistance may considerably
drop depending on the refrigerant volume in
the compressor, but this is not faulty.
(2) 1-2 seconds after a start:
FDCP2001 type: Approx. 32 A
FDCP2501 type: Approx. 37 A
40 Hz
65 Hz
75 Hz
104 ~ 107 167 ~ 173 180 ~ 190 195 ~ 197 198 ~ 203
Unit: V (AC)
80 Hz
95 Hz