Mitsubishi Heavy Industries SRK25GZ-L1 Handbook page 1051

2000 air conditioning & heat pump machinery handbook
Table of Contents

Advertisement

3) Face-to-face installation
Note (1) Make the air outlet the diagonal air outlet (standard) or the up air outlet (option).
4) Side-to-side & face-to-face installation
[Keep a space of more than 10 mm between the unit]
Note (1) Make the air outlet the diagonal air outlet (standard) or the up air outlet (option).
5) In the case where the unit is exposed to strong wind.
a) Face the unit air outlet at a 90º angle from the direction of the wind.
b) Securing outdoor unit (in the case of exposure to severe weather conditions)
Fix the unit in the following way.
Use overtuming prevention brackets.
Rig with wires.
Dimension
Distance
Item
Diagonal
Up air outlet
Dimension
Distance
Item
Diagonal
Up air outlet
(Use rigging wires that are resistant to corrosion and sufficient in
strength. For example SUS304-W1, wire thick-ness 2.9 mm)
FDC-HKXR
Unit: mm
L
L
1
2
1500 or more
1000 or more
500 or more
500 or more
Unit: mm
L
L
1
2
1500 or more
1000 or more
800 or more
800 or more
1049