Mitsubishi Heavy Industries SRK25GZ-L1 Handbook page 1001

2000 air conditioning & heat pump machinery handbook
Table of Contents

Advertisement

FDCP2501HKXRE2
Total capacity of indoor units operating simultaneously
Capacity Correction Calculations (The procedure for both cooling and heating is the same.)
Example Conditions
• Unit (50 Hz)
• Piping length (Shall be common among units) .......... 60 meters (suitable length)
• Difference in height between indoor and ........... 15 meters
• Air conditions .......... Outdoor air temperature 33˚CDB
Outdoor unit performance correction
1 Total connection capacity from indoor unit ... 90 1 unit + 140 1 unit + 28 1 unitt + 22 1 unit = 280
.
= 28kW (From table above)
.
2 Performance correction from indoor and outdoor temperatures
.
28
1.02 = 28.5kW
.
3 Performance correction from piping length and difference in height between indoor and outdoor units
.
28.5 (0.865 - 0.03) = 23.8kW (Actual performance)
.
Performance correction of indoor unit
Performance correction of indoor unit = System performance
[Example] FDTJ90HKXE2
90
.
23.8
= 7.65kW
.
280
Performance of indoor unit
FDTJ90HKXE2 ................... 7.65kW (Actual performance)
FDTJ140HKXE2 ................ 11.9kW (Actual performance)
FDTWJ28HKXE2B .......... 2.38kW (Actual performance)
FDTSJ22HKXE2B .......... 1.87kW (Actual performance)
Outdoor unit FDCP2501HKXRE2 1 unit
Indoor unit FDTJ90HKXE2 - 1 unit
FDTJ140HKXE2 - 1 unit
FDTWJ28HKXE2B - 1 unit
FDTSJ22HKXE2B - 1 unit
outdoor units
Indoor temperature 26˚CDB 19 ˚CWB
(Outdoor unit is lower)
Indoor unit capacity
Total capacity of indoor units
operating simultaneously
FDC-HKXR
Corrction when
cooling?
999