(b) If plural outdoor units are used
1) A maximum of 48 indoor units can be connected by using the crossover wiring method, with 2 wires for
each side of the outdoor and indoor units.
Outdoor unit
Indoor unit
2) Indoor/outdoor wiring method for multiple floors.
Outdoor
unit
3) Loop wiring is inhibited
Outdoor
Outdoor
unit
unit
Indoor
Indoor
unit
unit
(5) Remote controller wiring
(a) Wiring for controlling only one indoor unit.
X
Y
Z
Red White Black
X
Y
Z
Red White Black
Outdoor unit
A B
A B
A B
A B
Indoor unit
Outdoor
Outdoor
unit
unit
Indoor
Indoor
unit
unit
Indoor
Indoor
unit
unit
Outdoor
Outdoor
unit
unit
(No)
Indoor
Indoor
unit
unit
Indoor unit
terminal blocks
Note (1) Cables for the remote controller have polarity. Be sure
Remote controller
terminal blocks
Outdoor unit
Outdoor unit
A B
A B
2
Double cores 0.75 ~ 2 mm
Total length of signal wires: 1000 m or less
A B
A B
Indoor unit
Indoor unit
Outdoor
unit
Double cores 0.75 ~ 2 mm
Total length of signal wires: 1000 m or less
Indoor
unit
Indoor
unit
Loop wiring of signal wires is inhibiteed
Wiring at the Portion indicated by a
dotted line is inhibited.
to connect terminal blocks with the same numbers. If
mis wiring occurs, E1 is displayed and disables the
unit from operating.
FDC-HKXR
2
1061