Heatilator C40 Installation Manual page 33

Installation and fireplace setup epa certified woodburning fireplace
Hide thumbs Also See for C40:
Table of Contents

Advertisement

Flange
Termination Cap
Collar
2 in. (51 mm)
Minimum Height
Chase Top
Chimney
Pipe
Termination cap pipe and chimney section must overlap 1-1/2 in. (38 mm)
Figure 6.17 Installing an ST375 Square Termination Cap
Termination Cap
Collar
2 in. (51 mm)
Minimum Height
Chase Top
Chimney
Pipe
Termination cap pipe and chimney section must overlap 1-1/2 in. (38 mm).
Figure 6.18 Installing a TS345/TS345P Square Termination Cap
Heatilator • C40 Constitution • 480-2340 Installation Manual • Rev B 01-29-13
Place waterproof
caulk or sealer under
each flange of the
termination cap and
on top of each screw
to help prevent leaks.
The last section of pipe
must stop between 2 in. (51
mm) above the top of the
chase and 4 3/4 in. (121
mm) below the top of the
chase.
2 in. (51 mm)
maximum
4 3/4 in. (121 mm)
maximum
Chase
Place waterproof sealer under
each flange of the termination
cap and on top of each screw
to help prevent leaks.
The last section of pipe must
stop between 2 in. (51 mm)
above the top of the chase and
4 3/4 in. (121 mm) below the
top of the chase.
2 in. (51 mm)
maximum
4 3/4 in. (121 mm)
maximum
Chase
Remove 2 screws
from front & back
to lift the top off
Termination Cap
Collar
2 in. (51 mm)
Minimum Height
Chase Top
Chimney
Pipe
Termination cap pipe and chimney section must overlap
1-1/2 in. (38 mm)
Figure 6.19 Installing a TCT375 Terra Cotta Cap
Place waterproof sealer
under each flange of the
termination cap and on
top of each screw to
help prevent leaks.
The last section of pipe
must stop between 2 in.
(51 mm) above top of
chase and 7 in. (178 mm)
below top of chase
2 in. (51 mm)
7 in. (178 mm)
Chase
33