1.3

CABLE REQUIREMENTS

Cable
Video
Power
Control
1.4

POWER REQUIREMENTS

CyberScouts require a 24 VAC power supply to operate the pan/tilt drive,
camera, and blower. At 24 VAC, the CyberScout requires 6 VA of power.
Note: CyberScouts do not require isolated power inputs.
1.5

POWER CABLE SIZE AND LENGTH

CAUTION:
Choose the proper gauge of the cable to supply 24 volts to the
CyberScout. An inadequate gauge will cause a voltage drop
resulting in improper operation.
Table 1 provides the recommended cable lengths of varying wire gauges.
Table 1. Recommended maximum cable lengths
Maximum Cable Length
Wire Gauge
2
(awg)
(mm
)
10
2.60
12
2.05
14
1.62
16
1.29
18
1.02
20
0.81
22
0.64
1038864A / December 2002
Requirement
Coaxial (75 ohm)
24 VAC unshielded twisted-pair
Note: See Table 1 to determine the gauge and length.
RS422 unshielded twisted-pair cable
Note: The recommended cable size is 22 gauge (0.64 mm).
CyberScout
(6 VA)
Feet
Meters
7500
2288
4750
1450
3000
913
1875
575
1163
355
725
225
463
140