Product Design; Minimum Airflow Clearances - Goodman GSC130181A Technical Manual

Goodman gsc/vsc13 seer condensing units with r-22
Table of Contents

Advertisement

PRODUCT DESIGN

GSC/VSC 13 SEER models are available in 1 1/2 through 5
ton sizes. They are designed for 208/230 volt single phase
applications. Select GSC 3 phase models are available in
230V and/or 460V.
The condenser air is pulled through the condenser coil by a
direct drive propeller fan. This condenser air is then dis-
charged out of the top of the cabinet.
These units are designed for free air discharge, so no addi-
tional resistance like duct work shall be attached.
The suction and liquid line connections on present models
are of the sweat type for field piping with refrigerant type cop-
per. Back seating valves are factory installed to accept the
field run copper. The total refrigerant charge for a normal in-
stallation is factory installed in the condensing unit. GSC/
VSC units are charged for the matching evaporator coil and a
15 foot refrigerant line set.
Systems should be properly sized by heat gain and loss
calculations made according to methods of the Air Condi-
tioning Contractors Association (ACCA) or equivalent. It is
the contractors responsibility to ensure the system has ad-
equate capacity to heat or cool the conditioned space.
Some GSC/VSC condensing units use a mix of Copeland
®
Reciprocating
and Copeland Compliant
There are a number of design characteristics which are differ-
ent from the scroll compared to the traditional reciprocating
compressor.
Due to their design Scroll compressors are inherently more
tolerant of liquid refrigerant.
NOTE: Even though the compressor section of a Scroll com-
pressor is more tolerant of liquid refrigerant, continued flood-
back or flooded start conditions may wash oil from the bear-
ing surfaces causing premature bearing failure.
®
Copeland Compliant
Scroll compressors use white oil which
is compatible with 3GS. 3GS oil may be used if additional oil
is required.
The GSC/VSC condensers use new generation scroll com-
pressors, except for the VSC130181A*/B* and GSC130181C*
which use a rotary compressor. The scroll compressors have
an internal equalization mechanism and an anti-counter rota-
tion device which allow the scrolls to equalize in approxi-
mately ½ second at shut down.
Operating pressures, amp draws and minimum circuit am-
pacity may differ from standard reciprocating compressors.
This information may be found in the "Cooling Performance
Data" section and should be reviewed prior to installation of
the condenser.
GSC130361DF use Bristol
the most advanced compressors in the industry today. The
BENCHMARK™ reciprocating compressor can be recognized
by a "J" in the fourth character of the compressor model num-
ber. Innovative mechanical design and gas management make
the BENCHMARK™ compressor very efficient and remark-
ably quiet. The sound content (frequency) delivers excep-
tional acoustical characteristics and the virtually round hous-
ing design is compact and also helps to reduce the overall
sound and vibration.
4
®
Scroll compressors.
®
BENCHMARK™ compressors,
NOT
RECOMMENDED
B
A
AA
C
AA
AA
A
C

Minimum Airflow Clearances

Model Type
Residential
Light Commercial
Special consideration must be given to location of the con-
densing unit(s) in regard to structures, obstructions, other
units, and any/all other factors that may interfere with air
circulation. Where possible, the top of the unit should be
completely unobstructed; however, if vertical conditions re-
quire placement beneath an obstruction there should be a
minimum of 60 inches between the top of the unit and
the obstruction(s). The specified dimensions meet require-
ments for air circulation only. Consult all appropriate regula-
tory codes prior to determining final clearances.
Another important consideration in selecting a location for
the unit(s) is the angle to obstructions. Either side adjacent
the valves can be placed toward the structure provided the
side away from the structure maintains minimum service clear-
ance. Corner installations are strongly discouraged.
DO NOT locate the unit:
– Directly under a vent termination for a gas appliance.
– Within 3 feet of a clothes dryer vent.
– Where the refreezing of defrost water would create a
hazard.
– Where water may rise into the unit.
B
B
B
AA
C
AA
AA
AA
C
A
B
C
10"
10"
18"
12"
12"
18"
OK!
OK!
OK!
OK!
OK!
OK!
AA
20"
24"