Procom MN200EBC Owner's Operation And Installation Manual

Blue flame vent-free natural gas space heater

Advertisement

OW NE R ' S OPE RAT ION AND INSTA LLATION M ANUAL
MN200EBC MN200EHBC
MN300EBC MN300EHBC
WARNING
: Improper
adjustment, alteration, service or main-
ten an ce can cause injury or property
damage. Refer to this manual for correct
installation and operational procedures.
For assistance or additional information
consult a qualified installer, service agency,
or gas supplier.
WARNING:
This is an unvented gas-
fired heater. It uses air (oxygen) from the
room in which it is installed.Provisions
for adequate combustion and ventilation air
must be provided. Refer to Air For Combus-
tion and Ventilation section on page 5 of
this manual.
Continental Appliance Inc./US Office
5 Musick
4600 Highlands Parkway S.E.
Irvine
Suite# D/E
CA 92618
Smyrna GA 30080
Nanjing PRO-COM Electric Appliance Co.,Ltd.
#6 Chuangye Road,High New Tech.Zone,
Great Bridge Road North,Nanjing,210061,China.
TOLL FREE NUMBER: 1-877-886-5989
this manual is not followed exactly,
a f i r e o r e x p l o si o n ma y r e s u l t
causing property damage, personal
injury, or loss of life.
Do not store, or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
WHAT TO DO IF YOU SMELL GAS
l Do not try to light any appliance.
l Do not touch any electrical switch; do not
use any phone in your building.
l Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions.
installation,
l
call the fire department.
Installation and service must be performed
by a qualified installer, service agency or
gassupplier.
This appliance may be installed in an after-
market* permanently located, manufactured
(mobile) home, where not prohibited by local
codes.
This appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convertible for use with other
gases.
WATER VAPOR: A BY-PRODUCT OF UNVENTED
ROOM HEATERS
Water vapor is a by-product of gas combustion.An
unvented room heater products approximately one (1)
ounce (30ml) of water for every 1,000 BTU's(.3KW's)
of gas input per hour. Refer to page 4.
*Aftermarket: Completion of sale, not for purpose of
resale, from the manufacturer.
Installer: Please leave these instructions with the
consumer.
Consumer: Please retain these instructions for
future use.
BLUE FLAME V EN T-F RE E
WARNING
If the information in
:
If
you
cannot reach your gas supplier,
NATURAL GA S
SPACE H E AT E R
PR-MCL051-04-0506

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MN200EBC and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Procom MN200EBC

  • Page 1 Do not try to light any appliance. l Do not touch any electrical switch; do not use any phone in your building. MN200EBC MN200EHBC l Immediately call your gas supplier from a MN300EBC MN300EHBC neighbor’s phone. Follow the gas supplier’s instructions.
  • Page 2: Table Of Contents

    Table of Contents Safety Information..................2 Product Features..................3 Local Codes....................3 Unpacking....................4 Air for Combustion and Ventilation............5 Installation....................7 Connecting to Gas Supply............... 9 Checking Gas Connections..............10 Operating Your Heater................11 Cleaning & Maintenance.................14 Replacement Parts..................16 Specifications..................16 Troubleshooting..................17 Parts List......................20 SAFETY INFORMATION CARBON MONOXIDE POISON- Make certain you read and under-...
  • Page 3: Product Features

    AUTOMATIC IGNITION 4. This heater needs fresh, outside WARNING air ventilation to run properly. This SYSTEM Modeles MN200EBC MN200EHBC heater has an Oxygen Depletion MN300EBC MN300EHBC are This heater is equipped with an Sensor (ODS) safety shutoff equipped for Natural Gas. Field automatic control system.
  • Page 4: Unpacking

    PRODUCT FEATURES Touch Pad ON/OFF Switch Cabinet Top Burners Grill Guard Ignitor for Manual Overide Control System Lower Front Panel Door Satety Pilot Control Knob for Manual Overide Control System Figure1-Vent-Free Heater LOCAL CODES continued State of Massachusetts : The installation must be made by a licensed plumber or gas fitter in the Install and use heater with care.
  • Page 5: Air For Combustion And Ventilation

    Confined and Unconfined AIR FOR COMBUSTION Unusually Tight Construction Space The air that leaks around doors and AND VENTILATION windows may provide enough fresh The National Fuel Gas Code ANSI WARNING: This heater shall air for combustion and ventilation. Z223.1 defines a confined space as not be installed in a confined However, in buildings of unusually a space whose volume is less than...
  • Page 6 3. Add the Btu/Hr of all fuel burning appliances in the space. Vent-free heater Btu/Hr Gas water heater* Btu/Hr Example: Gas furnace Btu/Hr Gas water heater 40,000 Btu/Hr Vented gas heater Btu/Hr Vent free heater 18,000 Btu/Hr Gas Fireplace logs Btu/Hr Total 58,000...
  • Page 7: Installation

    INSTALLATION CAUTION: If you install the NOTICE: This heater is in- heater in a home garage tended for use as supplemental heater pilot and burner must heat. Use this heater along with be at least 18 inches above your primary heating system. Do floor.
  • Page 8 These two holes chor wings (see Figure 8). are 16 inches apart from their Model MN200EBC MN200EHBC centers. Attach mounting bracket to IMPORTANT: Do not ham- wall only in one of two ways: mer key! For thick walls (over 1/ Attaching to wall stud "...
  • Page 9: Connecting To Gas Supply

    INSTALLATION CONNECTING TO GAS *A CSA/AGA design-certified equip- SUPPLY " ment shutoff valve with 1/8 continued tap is an acceptable alternative to Installing Bottom Bracket (See WARNING: A qualified test gauge connection. Purchase Figure10) service person must connect the optional CSA/AGA design certi- 1.
  • Page 10: Checking Gas Connections

    INSTALLATION Pressure Testing Gas Supply Piping System Test Pressures In Excess Of 1/2 PSIG (3.5 K Pa) 1. Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage heater regulator.
  • Page 11: Operating Your Heater

    4. W ait five (5) minutes to clear out A. This appliance is equipped with an CHECKING GAS any gas. Then smell for gas, includ- ignition device which auto matically CONNECTIONS ing near the floor. If you smell gas, lights the pilot. Do not try to light Continued STOP! Follow “B”...
  • Page 12 OPERATING YOUR HEATER OPERATING BLOWER 3. Remove round access door of right continued Press BLOW ER button, for desired side panel. Push in control knob SETTING TIMER blower operation. slightly and turn clockwise to the AUTO: Blower will come on several AUTO ON: W ith burner off, press OFF position.
  • Page 13: Burner Flame Pattern

    MANUAL OPERATING MANUAL LIGHTING INSTRUCTIONS PROCEDURE continued (Match Light) 9. When electric power is available 1. Remove lower front panel. 2. Follow steps 1 through 5 under and elelectronic operation is Figure 16- Correct Pilot Flame Manual Operatting desired, turn clockwise Pattern Instructions on page 12.
  • Page 14: Cleaning & Maintenance

    To clean these parts we recom- mend using compressed air no CLEANING AND greater than 30 PSl. MAINTENANCE Your local computer store, hardware store, or home center may carry WARNING: Disconn ect compressed air in a can. You can power before attempting any main- use a vacuum cleaner in the blow tenance or cleaning to reduce the position.
  • Page 15 Figure 23- ( M o d e l M N 2 0 0 E B C M N 3 0 0 E B C ) Double Control Systems Diagram Figure 24- (Model MN200EHBC MN300EHBC)
  • Page 16: Replacement Parts

    (Propane/LP or Natural gas) purchase date FLOOR STAND MODEL: PF0920C warranty card Usually, we will ask you to return the defective part to the factory. SPECIFICATIONS MN300EBC(MN300EHBC) MN200EBC(MN200EHBC) 30,000 BTU/Hr 20,000 Natural Gas Only Gas Type Natural Gas Only Automatic(Automatic/Electric) Ignition...
  • Page 17: Troubleshooting

    TROUBLESHOOTING WARNING: If you smell gas Shut off gas supply. Do not try to light any appliance. Do not touch any electrical switch; do not use any phone in your building. Immediately cal l your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
  • Page 18 TROUBLESHOOTING Continued OBSERVED PROBLEM POSSIBLE CAUSE REMEDY ODS/pilot has flame, but burner(s) 1. Burner injector is clogged 1. Clean burner injector (see Cleaning does not light Maintenance, Page14) replace burner injector 2. Inlet gas pressure is too low Contact local natural gas company 3.
  • Page 19 TROUBLESHOOTING Continued REMEDY OBSERVED PROBLEM POSSIBLE CAUSE Ventilate room. Stop using odor Heater produces unwanted odors 1. Heater is burning vapors from causing products while heater paint, hair spray, glues, etc. is running (See IMPORTANT statement at beginning of troubleshooting) Locate and correct all leaks(see 2.
  • Page 20 ILLUSTRATED PARTS BREAKDOWN MN200EBC MN300EBC...
  • Page 21: Parts List

    PARTS LIST This list contains replaceable parts for your heater. W hen ordering relacement parts, following the instructions listed under Replacement Part on page16 of this MN200EBC manual. MN300EBC MN300EBC MN200EBC DESCRIPTION PART NO. PART NO. MCL001-01 MCL001-02 Rotating cover...
  • Page 22 ILLUSTRATED PARTS BREAKDOWN MN200EHBC MN300EHBC...
  • Page 23 PARTS LIST This list contains replaceable parts for your heater. W hen ordering replacement parts, following the instructions listed under Replacement Part on page16 of this MN200EHBC manual. MN300EHBC MN300EHBC MN200EHBC DESCRIPTION PART NO. PART NO. MCL001-01 MCL001-02 Rotating cover MCL008-01 MCL008-01 rotating cover dowel...

This manual is also suitable for:

Mn300ebcMn300ehbcMn200ehbc

Table of Contents