ALARMS
ALARMS/WARNINGS CODES
DISP
DISP
DESCRIPTION
CL40/
DC40
DC41
Antifreeze alarm.
- ECOLEAN Outlet temperature < 3ºC. Reset MAN.
A
- AIRCOOLAIR circuit indoor piping temperature <
2ºC. Reset AUTO.
A2
Antifreeze alarm, circuit 2. (Aircoolair only).
A2
Circuit 2 indoor piping temperature < 2ºC. Reset
AUTO.
Warning the high ambient temperature.
Ht
------
Ambient temperature > 40ºC.
Warning the low ambient temperature.
Lt
------
Disabled by default.
AHt
------
Not used.
HLt
------
Not used.
Warning the low power supply.
Power supply < 20.4V.
ELS
------
Warning the high power supply.
EHS ------
Power supply > 26.4V.
Not used.
Ed
------
Not used.
Ed2
------
Not used.
SH ------
SH2 ------
Not used.
nO
------
Not used.
nO2
------
Not used.
LO
------
Not used.
Not used.
LO2
------
Not used.
HA ------
Not used.
HA2 ------
EP
------
Not used.
EP2
------
Not used.
ES
------
Not used.
ES2
------
Not used.
EU ------
Not used.
Not used.
EU3 ------
Eb
------
Not used.
Eb2
------
Not used.
L
------
Not used.
Ed
------
Not used.
Ed2
------
Not used.
PH ------
Not used.
PH2 ------
Not used.
SUL ------
Not used.
Alarm, faulty communication between DC40 and
tEr
OcH
Climatic 40. (Aircoolair only).
Generic alarm.
AcH
Some active alarms on Climatic 40.
Ahu
Not used.
DC40 internal probe alarm.
AtE
Faulty internal probe.
CEr
DC40 setting error.
UEr
DC40 hardware error.
EFFECT
RE
-ECOLEAN
compressors
ECOLEAN: Reset and check:
stop.
- Check the water filter.
- Check water flow.
- AIRCOOLAIR
MAN/
- Check that the water pump is connected to power supply of the unit.
Close freecooling
AUTO
AIRCOOLAIR: Check:
air dumper and
- Indoor unit air filter.
stops circuit
- Air damper correctly working.
compressors
Close
freecooling air
Check:
dumper and
AUTO
- Indoor unit air filter.
stops circuit
- Air damper correctly working.
compressors 2
Check ambient probe location; avoid places where the measurement of
AUTO
------
the ambient temperature by the internal sensor may be altered.
Call SAT.
------
------
------
------
Call SAT.
------
------
Call SAT.
AUTO Check controller power supply = 24V (see electrical diagram).
------
Unit stops
AUTO Check controller power supply = 24V (see electrical diagram).
Call SAT.
------
------
Call SAT.
------
------
Call SAT.
------
------
------
------
Call SAT.
------
------
Call SAT.
------
------
Call SAT.
------
------
Call SAT.
Call SAT.
------
------
Call SAT.
------
------
Call SAT.
------
------
------
------
Call SAT.
------
------
Call SAT.
------
------
Call SAT.
------
------
Call SAT.
------
------
Call SAT.
Call SAT.
------
------
------
------
Call SAT.
------
------
Call SAT.
------
------
Call SAT.
------
------
Call SAT.
------
------
Call SAT.
------
------
Call SAT.
------
------
Call SAT.
------
------
Call SAT.
- DC40 connections (see electrical diagrams).
Unit stops
AUTO
Call SAT.
------
------
Check Climatic 40 alarm code and act by consequence.
------
------
Call SAT.
------
------
Call SAT.
------
------
Call SAT.
------
------
Call SAT.
26
ACTION