ALARMS
ALARM LOG
Climatic 40, has a log where significant events that stop (alarms) or limit (warnings) the operation of the unit, are saved.
In order to entry Alarm Log menu, do the same as explained in chapter 3 MENU in the paragraph PARAMETERS EDITING MENU,
introducing the password 44 instead of 22.
Up to 25 events can be saved, highlighting in order: event code, sart hours, start minutes, start day, start month, end hours, end
minutes, end day, end month.
EVENT CODE
START HOURS
START MINUTES
START DAYS
START MONTHS
END HOURS
END MINUTES
END DAYS
END MONTHS
WARNING
The alarm log is only active and operative if the clock board is fitted.
If there are no alarms saved, "noH" is displayed.