The Intelligent Defrost; Outdoor Pcb For Defrost - Chigo 38B Service Manual

Split wall-mounted type
Table of Contents

Advertisement

36
c o m p r e s s o r
d o o r
b l o w e r f a n
Defrost (only applicable to the heating mode)

1. the intelligent defrost

In the heating mode, the electric control board checks and compares the temperature of indoor room and indoor coil
pipe after the compressor works for a while; judge whether the outdoor heat exchanger part is frosted or not according to
conditions such as the change of indoor coil pipe temperature; if it is judged as frosted, it automatically enters defrosting
process. When defrosting, close the indoor and outdoor blower fan and four-way valve.

2. Outdoor PCB for defrost.

In the heating mode, the unit defrost by outdoor control board:
①unit start defrost shall all meet the following conditions:
a、compressor continuous running over 7 minutes;
b、defrost relay shut off; (-5℃)
c、compressor cumulate running time over 50 minutes.;
②first defrost interval time is 50 minutes, later defrost interval time decided by last defrost time.
Defrost time(minute)
15
10--15
7--10
3--7
≤3
(2)end defrost condition(meet one of follows)
a、defrost time have fifteen minutes.
b、defrost relay turn on; (>8℃)
c、press ON/OFF key in defrost process.
3. Outdoor sensor for defrost
Next defrost interval time(minute)
30
40
60
70
80
Tr
24

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents