R410A50Hz Universal Outdoor Series Technical Manual General Information R410A 50Hz Universal Outdoor series PART 1.General Information 1.Nomenclature ................2 2.Model Names of Indoor/Outdoor Units ........4 3.External Appearance ..............5 4.Features ..................7 GD Chigo Heating & Ventilation Equipment Co., Ltd.
1.10 Fire resistance design, the E-box with galvanized steel built-in body easy for maintenance. 1.11 Fresh air intake. 1.12 Multi protection and auto-restart function. 1.13 Standard for wireless controller; option for wired controller. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Indoor temp: 20° CDB; Outdoor temp: 7° CDB, 6° CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 14
Indoor temp: 20° CDB; Outdoor temp: 7° CDB, 6° CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. GD Chigo Heating & Ventilation Equipment Co., Ltd.
4.3 The outlet and the inlet are not impeded, and the influence of external air is the least. 4.4 The air flow can reach throughout the room. 4.5 The connecting pipe and drainpipe could be extracted out easily. 4.6 There is no direct radiation from heaters. GD Chigo Heating & Ventilation Equipment Co., Ltd.
1-phase Power Frequency and 220-240V, 50Hz Voltage Indoor Unit Power Wiring (mm 3×1.0mm 3×1.0mm 3×1.0mm Ground Wiring 1 mm 1 mm 1 mm Indoor/Outdoor Connecting Wiring Strong Electric 5×0.75mm 5×0.75mm 5×0.75mm Signal GD Chigo Heating & Ventilation Equipment Co., Ltd.
, and button is pushed the indoor unit when the ON/OFF then repeatly push the ON/OFF button is pushed button twice Buttons on the remote controller Press Reset button don’t work GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 40
Running lamp and Alarm lamp Indication Enforced cooling both flashing/5Hz Indication Anti- cool air in heating mode Defrosting preheat lamp Indication Defrosting Defrosting preheat lamp GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual Duct Type Indoor Unit 1.Features Low Static Pressure Duct Medium Static Pressure Duct High Static Pressure Duct GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 43
1.7 Two air return type option: air inlet from back is standard and from bottom is optional 1.8 Multi protection and auto-restart function. 1.9 Standard for wired controller, wireless controller for option. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Indoor temp: 20° CDB; Outdoor temp: 7° CDB, 6° CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 45
Indoor temp: 20° CDB; Outdoor temp: 7° CDB, 6° CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 46
Indoor temp: 20° CDB; Outdoor temp: 7° CDB, 6° CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 47
Indoor temp: 20° CDB; Outdoor temp: 7° CDB, 6° CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual Duct Type Indoor Unit 4.Service Space Ensure enough space required for installation and maintenance. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Fan fixing board assy Main control board Front hanger B PTC transformer hanger E-parts box cover assy Right clapboard Terminal Right end plate of Evaporator Upper cover Evaporator chassis Lower scroll case Front hanger A GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 88
Distributing capillary assy for indoor Front hanger A 30.2 unit Fan fixing board assy 30.3 Collecting pipe assy Lower scroll case 30.4 Installation tube for probe Axis2 30.5 Installation spring for probe GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 89
Welding assy for water collector 17.4 Terminal leading NO.7Line pressing buckle 17.5 effluent joint rubber cap E-parts box base Lower plate big cover plate Return air damper Right clapboard filter screen Right end plate of Evaporator GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 90
E-parts box cover assy leading Small cover plate effluent joint rubber cap E-parts box base Lower plate big cover plate Return air damper Right clapboard filter screen Right end plate of Evaporator GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 91
Evaporator assemble left clapboard Right clapboard Fan fixing board assy hanger fan assy E-parts box cover assy 15.1 fan motor E-parts 15.2 scroll case(left) GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 92
Evaporator assemble left clapboard Right clapboard Fan fixing board assy hanger fan assy E-parts box cover assy 15.1 fan motor E-parts 15.2 scroll case(left) GD Chigo Heating & Ventilation Equipment Co., Ltd.
Outdoor temperature is lower than 7℃ Close doors and windows Low heating effect Door and windows not completelty closed Check leakage and rightly recharge Leakage of refrigerant or lack of refrigerant refrigerant GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 94
Outdoor coil temperature sensor fault Fault problem resolved Fault Water full protection Outdoor protection Fault Fault Communication fault Manual eliminate Recovery after interruption Fault EEPROM communication fault of power supply Indication Enforced cooling GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 95
R410A50Hz Universal Outdoor Series Technical Manual Duct Type Indoor Unit Indication Anti- cool air in heating mode Indication Defrosting GD Chigo Heating & Ventilation Equipment Co., Ltd.
1.4 Washable air filter 1.5 Adopting waterproof plastic film on water collector, avoiding water leakage. 1.6 Self-diagnostic function and multi protection. 1.7 Auto-restart function. 1.8 Standard for wireless controller; option for wired controller GD Chigo Heating & Ventilation Equipment Co., Ltd.
Indoor temp: 20° CDB; Outdoor temp: 7° CDB, 6° CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 99
Indoor temp: 20° CDB; Outdoor temp: 7° CDB, 6° CWB; Equivalent ref. Piping: 7.5m(horizontal) 3.Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 114
Lelf separating board pipe temperature probe Indoor fan motor(left) indoor temperature probe connecting wire of display lamp left mounting plate of evaporator panle outlet holder Rear cover holder evaporator E-part box holder water pan GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 115
Motor separating board 23.4 Vertical step motor Wheel volute for slim type 23.5 Horizontal step motor Indoor fan motor 23.6 End bearing of louver Air inlet grille 23.7 Intermediate bearing of louver GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 116
9.10 endbearing of louver right mounting plate of evaporator 9.11 intermediate bearing of louver evaporator 9.12 driving lever for louver shunt capillary assembly 9.13 follower lever for louver 29.1 GD Chigo Heating & Ventilation Equipment Co., Ltd.
Indoor temp: 20° CDB; Outdoor temp: 7° CDB, 6° CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 124
Indoor temp: 27° CDB, 19° CWB; Outdoor temp: 35° CDB; Equivalent ref. Piping: 7.5m(horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20° CDB; Outdoor temp: 7° CDB, 6° CWB; Equivalent ref. Piping: 7.5m(horizontal) GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual Outdoor unit 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. 2.Dimensions 2.1 COU-18H B=(370) D=(590) A=(875) 2.2 COU-24HR1 GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 126
R410A50Hz Universal Outdoor Series Technical Manual Outdoor unit GD Chigo Heating & Ventilation Equipment Co., Ltd.
(Wall or obstacle) Obstacle Air inlet >30cm Fix with bolt Air inlet Maintain channel >60cm Air outlet Deep foundation Necessary width 300mm is necessary between 2 outdoor units 300mm M10 bolt 4pieces per unit GD Chigo Heating & Ventilation Equipment Co., Ltd.
1.0m Note: H= 0.5 × height of outdoor unit Note: The point A is in the middle of the whole outdoor panel. Model Noise level dB(A) COU-18HR1 COU-24HR1 COU-36HR1 COU-36HSR1 COU-48HSR1 COU-60HSR1 GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 146
24.2 Sequence protector Top net 24.3 Contactor Handle 24.4 Fan motor capacitor Front panel 24.5 Terminal Propeller fan 24.6 Groove clamp Asynchronous motor Plastic rear net Fan motor support Refrigerant R410a 3.6kg GD Chigo Heating & Ventilation Equipment Co., Ltd.
1.5. Be sure of no leakage by checking it with leak detector or soap water. 1.6. Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath (fittings), and bind it well with the tapes to prevent leakage. GD Chigo Heating & Ventilation Equipment Co., Ltd.
If it rises, it shows there’s moisture or leakage point. Vacuuming from liquid pipe and gas pipe at the same time. Sketch map of common vacuum dry procedure. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 150
Determinant: Pass if achieving below -755mmHg. If -755mmHg can’t be achieved in 2h, repeat procedure ③ and ④. ⑤. Vacuum placing test · · · · · · 1h ⑥. Sketch map of special vacuum dry procedure GD Chigo Heating & Ventilation Equipment Co., Ltd.
— — Added Refrigerant When 30g/m×(L-5) 65g/m×(L-5) 120g/m×(L-5) Over 5m(One-way) Remark: R (g): Additional refrigerant to be charged L (m): The length of the refrigerant pipe (one-way) D (mm): Liquid side piping GD Chigo Heating & Ventilation Equipment Co., Ltd.
4.2.1. If the pressure at the connection of the drainpipe is negative, it needs to design drainpipe trap. 4.2.2. Every indoor unit needs one drainpipe trap. 4.2.3. A plug should be designed to do cleaning. P l u g GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 153
Calculate allowed volume =Total cooling capacity of indoor units(HP)×2 (l/ hr) Allowed volume(lean 1/50) (l/ hr) I.D. (mm) Thick Hard PVC ∽≤14 ¢25 集中排水管 Hard PVC 14<∽≤88 ¢30 Hard PVC 88<∽≤334 ¢40 Hard PVC 175<∽≤334 ¢50 334<∽ Hard PVC ¢80 GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 154
Turn off the power and drain the remained water, and then turn on the air conditioner. Note: the drain stuff in the main water receipt plate is for maintenance. Stuff up the drain stuff to prevent water leakage. GD Chigo Heating & Ventilation Equipment Co., Ltd.
5.2.2. Insulation for non-jointing parts and non-connection parts wrong right Gas pipe and liquid pipe should Insulate the gas pipe Insulate the gas pipe and not be put together to insulate (cooling only) liquid pipe GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 156
5.4.2 The gas and liquid pipe should be heat insulated individually, the connecting part should be heat insulated individually. 5.4.3 Use the attached heat-insulation material to insulate the pipe connections (pipes’ tie-in ,expand nut ) of the indoor unit GD Chigo Heating & Ventilation Equipment Co., Ltd.
Whether there is vibration or abnormal noise during operation. Whether the generated wind, noise, or condensed of by the air conditioner have influenced your neighborhood. Whether any of the refrigerant is leaked. GD Chigo Heating & Ventilation Equipment Co., Ltd.
It will cancel damp, purification, sleep, turbo and timing running mode. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 160
Pressing MODE key can’t cancel timing in timing mode which will send out the order of timing time by pressing other key. I. TURBO key: GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 161
Press the key when the remote control is closed, the control will switch modes in the order: CLEAN →cancel CLEAN→ CLEAN; when you stop the unit and turn on the purification switch, except the wind, the stable swing and air door swing speed aren’t adjusted. GD Chigo Heating & Ventilation Equipment Co., Ltd.
“MODE” key- The key works as the “MODE” key in the remote controller; c. “SPEED” key- The key works as the “SPEED” key in the remote controller; d. “TIMING” key- The key works as the “TIMING” key in the remote controller; GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 163
4. Buzzer: The buzzer will utter three times when power-on and starting and it will utter twice when pressing “TIME +” and “TIME -” key at the same time. When the controller accepts other signal, it only utters once. 2.2 ZKX-PF-02 GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 164
OFF state, and "TIMING OFF"and "TIMING"lamps will be on. 2) Press + or - button to set the desired timing OFF time. The set time ranges From 1 to 12 hours. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 165
During the operation of heating mode, the room temperature will be dropped gradually 5℃(9 ℉)lower than the setting after the machine begins to operate in the sleeping mode. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 166
R410A50Hz Universal Outdoor Series Technical Manual control 更新日志: 2012.2.9 By Zack 18K(含 18K)机器是由内机供电,24K(含 24K)以上是内外机分别供电。 2012.3.22 By Zack 更改为新电控。 GD Chigo Heating & Ventilation Equipment Co., Ltd.