R410A50Hz Universal Outdoor Series Technical Manual General Information R410A 50Hz Universal Outdoor series PART 1.General Information 1.Nomenclature ................2 2.Model Names of Indoor/Outdoor Units ........3 3.External Appearance ..............4 4.Features ..................6 GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual General Information 1.Nomenclature 1.1. Indoor unit 1.2. Outdoor unit GD Chigo Heating & Ventilation Equipment Co., Ltd.
(4) Intelligent auto-swing function, three modes for choice. Standard mode Anti-point blow mode Ceiling against mode (5) 3 fan speed,meet for different requirement. New streamlined fan design. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 12
(8) Easy and convenient installation and maintenance, washable filter design. (9) Built-in water pump, water head up to 700mm. 700mm (10) Fire resistance design, the E-box with galvanized steel built-in body easy for maintenance. GD Chigo Heating & Ventilation Equipment Co., Ltd.
(4) 4-way air flow, cold air can reach each corner of the room, providing a stable and comfortable environment. (5) Intelligent auto-swing function, three modes for choice. Standard mode Anti-point blow mode Ceiling against mode GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 14
(6) 3 fan speed,meet for different requirement. New streamlined fan design. (8) Energy saving and healthy, adopting hydrophilic aluminum fins increasing heat-exchange efficiency. (9) Easy and convenient installation and maintenance, washable filter design. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 15
Add 4 interfaces in body, can be connected with duct to another room. Fresh air makes air quality more healthy and comfortable. (13) Multi protection and auto-restart function. (14) Standard for wireless controller; option for wired controller. Standard optional GD Chigo Heating & Ventilation Equipment Co., Ltd.
2.7/4.0 2.7/4.0 5.4/8.0 Max pressure Refrigerant type R410A R410A R410A Φ6.35/Φ12.7 Φ6.35/Φ12.7 Φ9.52/Φ15.88 Refrigerant piping Liquid side/Gas side Drainage pipe DN25 DN25 DN25 Standard controller Standard for remote controller(wired controller for option) GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 17
Inner grooved Coil length x height 2000×168×26.7 2000×252×26.7 2000×252×26.7 2000×252×40.1 x width Number of circuits Indoor air flow(High speed) 1200 1700 1900 1900 Indoor noise level dB(A) 44~48 44~48 45~52 45~52 GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 18
Indoor temp: 20° CDB; Outdoor temp: 7° CDB, 6° CWB; Equivalent ref. Piping: 7.5m(horizontal) 3.Actual noise level may differ, depending on the room structure, etc. since these noise values are from an anechoic room. GD Chigo Heating & Ventilation Equipment Co., Ltd.
4.3 The outlet and the inlet are not impeded, and the influence of external air is the least. 4.4 The air flow can reach throughout the room. 4.5 The connecting pipe and drainpipe could be extracted out easily. 4.6 There is no direct radiation from heaters. GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual Duct Type Indoor Unit 1. Features Low Static Pressure Duct Medium Static Pressure Duct High Static Pressure Duct GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 49
29dB(A). 3. Three fan speed, meet different requirement. 4. Filter can be taken out easily for clear. Easy maintenance. 5. E-box is body-side design, convenient installation and maintenance. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 50
Optional 1.2 Medium ESP Ducted Unit 1. Ultra-thin body design. 2. Adopting aviation centrifugal fans, and CFD technology design, increasing air-volume and decreasing noise level. 3. Three fan speed, meet different requirement. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 51
7. Two air return type option: air inlet from back is standard and from bottom is optional 8. Multi protection and auto-restart function. 9. Standard for wired controller, wireless controller for option. Standard Optional GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 52
(2) 120Pa ESP design, flexible air duct installation. (3) Filter can be taken out easily for clear. Easy maintenance. (4) Multi protection and auto-restart function. (5) Standard for wired controller, wireless controller for option. Standard Optional GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 56
Indoor temp: 20° CDB; Outdoor temp: 7° CDB, 6° CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual Duct Type Indoor Unit 4. Service Space Ensure enough space required for installation and maintenance. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Fan fixing board assy Eletronic control board for indoor Motor support assy unit 27.1 No.13 Bearing holder Plastic base for PCB Transformer 27.2 Motor support Small rubber ring that through Axis2 the coils Coupling GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 92
NO.7Line pressing buckle 17.5 effluent joint rubber cap E-parts box base Lower plate big cover plate Return air damper Right clapboard filter screen Right end plate of Evaporator Upper plate Return air assy GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 93
E-parts box base Lower plate big cover plate Return air damper Right clapboard filter screen Right end plate of Evaporator Return air assy Upper plate return air upper-lower rail 10.1 GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 94
13.2.2 Indoor Pipe temp sensor Base plate assy 13.3 transformer Water pan assy 13.4 Terminal Evaporator assy Right clapboard assy Pipe clamp Right wind wheel scroll case φ20 upper Pipe clamp 12.1 GD Chigo Heating & Ventilation Equipment Co., Ltd.
1. Flexible installation, ceiling suspended and floor standing. 2. Adopting centrifugal fans, higher ESP and longer air flow distance. 3. Two way auto-swing function, built-in two louver motor, vertical and horizontal air-flow adjustment. 4. Washable air filter GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 98
7. Water pump optional, pumping head is up to 1200mm. 8. Adopting waterproof plastic film on water collector, avoiding water leakage. 9. Self-diagnostic function and multi protection; Auto-restart function. 10. Standard for wireless controller; option for wired controller Standard Optional GD Chigo Heating & Ventilation Equipment Co., Ltd.
Standard controller Standard for remote controller(wired controller for option) Operation temp ° C 16~32 16~32 16~32 Ambient temp ° C -7~43 -7~43 -7~43 Application area 20-35 28-50 40-70 Stuffing Quantity(20'/40'/40'HQ) 132/270/306 75/165/189 75/165/189 GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 100
Indoor temp: 20° CDB; Outdoor temp: 7° CDB, 6° CWB; Equivalent ref. Piping: 7.5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Display lamp panel Evaporator left positioning plate Front panel component Evaporator assy 70 filter mound layer 2 Water pan components 70 filter Fan wheel(left) 70 grille Weld assembly for fan wheel mounting plate GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 116
Water outlet rubber cover 23.10 Louver holder Supporting board for motor 23.11 Guard vane Weld assembly intermediate Upper horizontal louver transverse girder Right mounting plate of evaporator Down horizontal louver Right cover GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 117
Single Connector left retaining plate left mounting plate of evaporator right retaining plate weld assembly of Water drain pan filter snap-gauge 32.1 water outlet rubber cover air inlet grille remote controller Filter GD Chigo Heating & Ventilation Equipment Co., Ltd.
(Wall or obstacle) Obstacle Air inlet >30cm Fix with bolt Air inlet Maintain channel >60cm Air outlet Deep foundation Necessary width 300mm is necessary between 2 outdoor units 300mm M10 bolt 4pieces per unit GD Chigo Heating & Ventilation Equipment Co., Ltd.
Note: H= 0.5 × height of outdoor unit Note: The point A is in the middle of the whole outdoor panel. Model Noise level dB(A) COU-12HR1 COU-18HR1 COU-24HR1 COU-36HR1 COU-36HSR1 COU-48HSR1 COU-60HSR1 GD Chigo Heating & Ventilation Equipment Co., Ltd.
1.5. Be sure of no leakage by checking it with leak detector or soap water. 1.6. Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath (fittings), and bind it well with the tapes to prevent leakage. GD Chigo Heating & Ventilation Equipment Co., Ltd.
If it rises, it shows there’s moisture or leakage point. Vacuuming from liquid pipe and gas pipe at the same time. Sketch map of common vacuum dry procedure. GD Chigo Heating & Ventilation Equipment Co., Ltd.
● When charging a system, care shall be taken that its maximum permissible charge is never exceeded, in view of the danger of liquid hammer. ● Charging with an unsuitable substance may cause explosions and accidents, so always ensure that the appropriate refrigerant is charged. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 148
— — Added Refrigerant When 30g/m×(L-5) 65g/m×(L-5) 120g/m×(L-5) Over 5m(One-way) Remark: R (g): Additional refrigerant to be charged L (m): The length of the refrigerant pipe (one-way) D (mm): Liquid side piping GD Chigo Heating & Ventilation Equipment Co., Ltd.
4.2.1. If the pressure at the connection of the drainpipe is negative, it needs to design drainpipe trap. 4.2.2. Every indoor unit needs one drainpipe trap. 4.2.3. A plug should be designed to do cleaning. P l u g GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 150
Allowed volume(lean 1/50) (l/ hr) I.D. (mm) Thick Hard PVC ∽ ≤14 ¢25 集中排水管 Hard PVC 14<∽ ≤88 ¢30 Hard PVC 88<∽ ≤334 ¢40 Hard PVC 175<∽ ≤334 ¢50 Hard PVC 334<∽ ¢80 GD Chigo Heating & Ventilation Equipment Co., Ltd.
Turn off the power and drain the remained water, and then turn on the air conditioner. Note: the drain stuff in the main water receipt plate is for maintenance. Stuff up the drain stuff to prevent water leakage. GD Chigo Heating & Ventilation Equipment Co., Ltd.
5.2.2. Insulation for non-jointing parts and non-connection parts wrong right Gas pipe and liquid pipe should Insulate the gas pipe Insulate the gas pipe and not be put together to insulate (cooling only) liquid pipe GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 153
5.4.2 The gas and liquid pipe should be heat insulated individually, the connecting part should be heat insulated individually. 5.4.3 Use the attached heat-insulation material to insulate the pipe connections (pipes’ tie-in ,expand nut ) of the indoor unit GD Chigo Heating & Ventilation Equipment Co., Ltd.
Whether there is vibration or abnormal noise during operation. Whether the generated wind, noise, or condensed of by the air conditioner have influenced your neighborhood. Whether any of the refrigerant is leaked. GD Chigo Heating & Ventilation Equipment Co., Ltd.
25℃ and the mode , wind speed, swing and air door are all automatic and there is no lamp, no turbo, no purification, no sleep, no timing and no hold function ). When it is not GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 157
Pressing MODE key can’t cancel timing in timing mode which will send out the order of timing time by pressing other key. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 158
CLEAN →cancel CLEAN→ CLEAN; when you stop the unit and turn on the purification switch, except the wind, the stable swing and air door swing speed aren’t adjusted. GD Chigo Heating & Ventilation Equipment Co., Ltd.