Page 3
Vacuum Dry and Leakage Checking .............. 59 Refrigerant charge ..................61 Water Drainage ....................62 Insulation Work ....................63 Test Operation ....................65 Part 5. Control System ..........66 Control function ....................66 Controller ......................70 GD Chigo Heating & Ventilation Equipment Co., Ltd.
1.3.1 Total new design for the E-box. Optimizing design of the E-box, fresh air cooling down the temperature of the inverter module. 1.3.2 Adopting high performance main chip of NEC for the electronic control, higher reliability and operation speed. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 5
1.5.1 Different indoor units for choice. You can choose different indoor units appearance for your favorite. 1.5.2 Much more indoor units for free combination, meeting for different requirement such as office, house use, villa and etc. 1.5.3 One or more indoor units’ connection combination for your choice. GD Chigo Heating & Ventilation Equipment Co., Ltd.
The different style panels can satisfy your different requirements. All the units have various functions, such as the function of auto-restart, sleep mode are standard, golden fins and some filter for optional. GD Chigo Heating & Ventilation Equipment Co., Ltd.
3. Sound level: measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions. 4. The above data may be changed without notice for future improvement on quality and performance. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 15
3. Sound level: measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions. 4. The above data may be changed without notice for future improvement on quality and performance. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 16
3. Sound level: measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions. 4. The above data may be changed without notice for future improvement on quality and performance. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Installation plate Indoor unit outline mm or 120 mm or more to wall more to wall Right rear side refrigerant pipe hole Left rear side refrigerant pipe hole Model A(mm) B(mm) ≤12000Btu/h ≥18000Btu/h GD Chigo Heating & Ventilation Equipment Co., Ltd.
Commu nica tion choice Models M107 TO ou tdoor Type choice2 Remark: 1、Make Memory short-circuit is a power outage memory otherwise for nothing 2、According to the specific models to dial the code GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 20
1 2 3 1 2 3 Remarks Remarks ON OFF OFF OFF Remark: 1、Make Memory short-circuit is a power outage memory otherwise for nothing 2、According to the specific models to dial the code GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A DC Inverter Multi-split Technical Manual Indoor Units 7. Air Velocity and Temperature Distributions Air velocity 1.5m/sec 0.5m/sec Temperature 27° C 22° C GD Chigo Heating & Ventilation Equipment Co., Ltd.
CSG-18HVR1(107) 220-240 V 3.15 0.027 0.19 Remark: MCA: Min. Current Amps. (A) MFA: Max. Fuse Amps. (A) KW: Fan Motor Rated Output (kW) FLA: Full Load Amps. (A) IFM: Indoor Fan Motor GD Chigo Heating & Ventilation Equipment Co., Ltd.
1.2 Soft start, the start current of the compressor is small and smooth. 1.3 Easy piping and wiring connection, no welding and only flare nut connection which makes the installation work easy and convenient. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Liquid side/ Gas side Ф6.35/Ф9.52 Ф6.35/Ф9.52 Refrigerant piping Max. pipe length (Between each IU and OU) Max. height difference Power wiring Connection wiring Signal wiring ˚C Ambient temperature -15~46 -15~46 Application area 26~30 35~43 GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 37
3. Sound level: measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions. 4. The above data may be changed without notice for future improvement on quality and performance. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 38
Refrigerant piping Liquid side/ Gas Ф6.35/Ф9.52 Ф6.35/Ф9.52 Max. pipe length (Between each IU and side Max. height Power wiring difference Connection wiring Signal wiring ˚C Ambient temperature -15~46 -15~46 Application area 39~45 52~65 GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 39
3. Sound level: measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions. 4. The above data may be changed without notice for future improvement on quality and performance. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Shutoff Valve EXVC temp sensor valve Condenser Coil temp Capillary Filter C 4-way sensor Liquid valve C valve Oil separator Gas valve A Gas valve B Shutoff Compressor valve Gas valve C GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A DC Inverter Multi-split Technical Manual Outdoor Units 6. Wiring Diagrams Inductor T rans in ainboard Model T ransformer T ransformer BL 14AWG YE 14AWG R D 14AWG P-LB GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A DC Inverter Multi-split Technical Manual Outdoor Units 12.Exploded View C2OU-14HVR1C2OU-18HVR1 GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 54
Left vertical shaft Connecting pipe B of Four-way valve Large hand-drawn Connecting pipe C of Four-way valve Top cover plate Valve seat assembly Valve seat guard cover DN4 Stop valve B 10.1 GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 55
R410A DC Inverter Multi-split Technical Manual Outdoor Units C3OU-21HVR1C3OU-27HVR1 GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 56
Fixing tube of condenser main outlet pipe Amorphous inductor (ROHS)Adfluxion pipe assy (ROHS)Eliminator 17.1 (ROHS)Adfluxion pipe A Small handle 17.2 (ROHS)Adfluxion pipe B Propeller fan 17.3 (ROHS)Adfluxion pipe C Plastic front net 17.4 DN8 Copper adapter with holder GD Chigo Heating & Ventilation Equipment Co., Ltd.
Normal operation for these modes not start immediately ①Improper temperature setting ①Reset temperature Unit functions but does not perform ②Unit capacity in sufficient for load or ②Consult your dealer sufficiently room size GD Chigo Heating & Ventilation Equipment Co., Ltd.
One indoor unit two indoor units Nominal 12+12 Capacity 9+12 K Btu/h 7+12 DC inverter multi system connect different style indoor units, includes 84series、 87series、107series. All type indoor units can be freely combined. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 59
7+7+9 7+12+12 K Btu/h 7+12 9+18 7+7+12 9+9+9 7+18 7+9+9 9+9+12 DC inverter multi system connect different style indoor units, includes 84series、 87series、 107series. All type indoor units can be freely combined. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation to do no damage to the tubing. Connect the pipes. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 61
Be sure of no leakage by checking it with leak detector or soap water. Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath (fittings), and bind it well with the tapes to prevent leakage. GD Chigo Heating & Ventilation Equipment Co., Ltd.
5 after the evacuation is complete, fully closethe handle Lo of the manifold valve and stopthe operation of the vacuum pump. Makeevacuation for 15 minutes or more and checkthat the compound meter indicates-76cmHg (-1x105Pa). GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 63
Apply a soap water or a liquid neutral detergent on the indoor unit connectionor outdoor unit connections by a soft brush to check for leakage of the connectingpoints of the piping. If bubblescome out, the pipes have leakage. ● Leak detector Use the leak detector to check for leakage. GD Chigo Heating & Ventilation Equipment Co., Ltd.
The additional refrigerant charge is simply related with the liquid pipe diameter. In the up formula, “L” means the length of liquid pipe between each indoor unit and outdoor unit (unit: m). GD Chigo Heating & Ventilation Equipment Co., Ltd.
The dimension of drainpipe can’t less than the connecting dimension of indoor drainpipe. Heat-insulation should be done well to prevent condensation. Indoor units with different drainage type can’t share one convergent drainpipe. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Insulate for the jointing area, expanding area and the flange area Insulate for the jointing area, expanding area and the flange area should be done after checking leakage of the pipes GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 67
The gas and liquid pipe should be heat insulated individually, the connecting part should be heat insulated individually. Use the attached heat-insulation material to insulate the pipe connections (pipes’ tie-in ,expand nut ) of the indoor unit. GD Chigo Heating & Ventilation Equipment Co., Ltd.
● Press the Manual control button to select the AUTO or COOL, the unit willoperate under Forced AUTO or COOL mode(see User Manual for details). 4. The test operation should last about 30 minutes. Installation sketch diagram of connecting pipes and connecting lines for Dual split type unit: GD Chigo Heating & Ventilation Equipment Co., Ltd.
Indoor unit off and display SCR Over-zero protection Indoor unit off and display (Available when using PG motor) EEPROM malfunction Indoor unit off and display (Mode confliction) Indoor unit off and display GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 70
High / low pressure switch protection Outdoor coil temperature too high protection (Only available in cooling mode) AC power voltage abnormal protection(Voltage too high or too low) Low temperature of the outdoor environment protection (cancel) GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 71
Zero-cross protection (For PG motor ) code is displayed Indoor units shut down, only the corresponding EPROOM fault code is displayed Indoor units shut down, only the corresponding Modes conflict hint code is displayed GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 72
Note 4:when cooling,it shows the average temperature T2B, when heating,it shows the average temperature Note 5: electronic expansion valves opening degree divided by 8 shows. Such as 480 P is revealed to 60. GD Chigo Heating & Ventilation Equipment Co., Ltd.
.when air-conditioner’s cooling-only model,the HEAT is for FAN, 2. When TURBO operation is selected ,room temperature is not controlled with operation being continually. If you feel the room temperature is too cool or too heat,please cancel the TURBO operation. GD Chigo Heating & Ventilation Equipment Co., Ltd.
3. After the setting of the timed switch-on,the digits shown on the display screen will go down by 1 for every elapsed hour.The display digits indicate the remaining time prior to the timed switch-on. GD Chigo Heating & Ventilation Equipment Co., Ltd.
2、During the defrosting,the outdoor unit might generate some steam.It is caused by fast defrosting , which is not a performance failure. 3、Upon the completion of the defrosting process,the heating operation is resumed. GD Chigo Heating & Ventilation Equipment Co., Ltd.