R410A50Hz Universal Outdoor Series Technical Manual General Information R410A 50Hz Universal Outdoor series PART 1.General Information 1.Nomenclature ....................2 2.Model Names of Indoor/Outdoor Units ............4 3.External Appearance ..................6 4.Features ......................7 GD Chigo Heating & Ventilation Equipment Co., Ltd.
230mm for standard cassette , save installation space. (3) 4-way air flow, cold air can reach each corner of the room, providing a stable and comfortable environment. (4) 3 fan speed,meet for different requirement. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 14
4 -way Cassette Indoor Unit New streamlined fan design. Compact Cassette Standard Cassette (6) Energy saving and healthy, adopting hydrophilic aluminum fins increasing heat-exchange efficiency. (7) Easy and convenient installation and maintenance, washable filter design. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 15
This function is available for standard cassette. (11) Multi protection and auto-restart function. (12) Standard for wireless controller; option for wired controller. \ (13) Standard optional GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 22
Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc. since these noise values are from an anechoic room. GD Chigo Heating & Ventilation Equipment Co., Ltd.
4.3 The outlet and the inlet are not impeded, and the influence of external air is the least. 4.4 The air flow can reach throughout the room. 4.5 The connecting pipe and drainpipe could be extracted out easily. 4.6 There is no direct radiation from heaters. GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual Duct Type Indoor Unit 1. Features Low Static Pressure Duct Medium Static Pressure Duct High Static Pressure Duct GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 51
4. Filter can be taken out easily for clear.Easy maintenance. 5. E-box is body-side design, convenient installation and maintenance. 6. Multi protection and auto-restart function. 7. Standard for wired controller, wireless controller for option.. Standard Optional GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 52
4. 30Pa ESP design for the medium static pressure duct type, duct connected installation meet for different room structure. 70pa is optional. 5. Filter can be taken out easily for clear.Easy maintenance. 6. E-box is body-side design, convenient installation and maintenance. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 53
7. Two air return type option:air inlet from back is standard and from bottom is optional 8. Multi protection and auto-restart function. 9. Standard for wired controller, wireless controller for option. Standard Optional GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 54
(2) 120Pa ESP design, flexible air duct installation. (3) Filter can be taken out easily for clear.Easy maintenance. (4) Multi protection and auto-restart function. (5) Standard for wired controller, wireless controller for option. Standard Optional GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 58
2.Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 5m(horizontal) 3.Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A50Hz Universal Outdoor Series Technical Manual Duct Type Indoor Unit 4. Service Space Ensure enough space required for installation and maintenance GD Chigo Heating & Ventilation Equipment Co., Ltd.
3.1.6 input pipe assy 3.1.7 the fixed hanger of evaporator 3.1.8 the right side plate component the right cover plate of air return box upper foam the top cover component GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 88
11.6 transformer 11.7 the resistance of motor connecting the fixed plate component the cover assy for output pipe the left side plate component the bottom plate of air return box GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 89
NO.7Line pressing buckle 17.5 effluent joint rubber cap E-parts box base Lower plate big cover plate Return air damper Right clapboard filter screen Right end plate of Evaporator Upper plate Return air assy GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 90
E-parts box base Lower plate big cover plate Return air damper Right clapboard filter screen Right end plate of Evaporator Return air assy Upper plate return air upper-lower rail 10.1 GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 91
13.2.2 Indoor Pipe temp sensor Base plate assy 13.3 transformer Water pan assy 13.4 Terminal Evaporator assy Right clapboard assy Pipe clamp Right wind wheel scroll case φ20 upper Pipe clamp 12.1 GD Chigo Heating & Ventilation Equipment Co., Ltd.
1. Flexible installation, ceiling suspended and floor standing. 2. Adopting centrifugal fans, higher ESP and longer air flow distance. 3. Two way auto-swing function, built-in two louver motor, vertical and horizontal air-flow adjustment. 4. Washable air filter GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 95
7. Water pump optional, pumping head is up to 1200mm. 8. Adopting waterproof plastic film on water collector,avoiding water leakage. 9. Self-diagnostic function and multi protection; Auto-restart function. 10. Standard for wireless controller; option for wired controller Standard Optional GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 98
Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 5m(horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 115
Water outlet rubber cover 23.10 Louver holder Supporting board for motor 23.11 Guard vane Weld assembly for intermediate Upper horizontal louver transverse girder Right mounting plate Down horizontal louver evaporator Right cover GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 116
Single Connector left retaining plate left mounting plate of evaporator right retaining plate weld assembly of Water drain pan filter snap-gauge 32.1 water outlet rubber cover air inlet grille remote controller Filter GD Chigo Heating & Ventilation Equipment Co., Ltd.
3.Service Space (Wall or obstacle) Obstacle Air inlet Fix with bolt Maintain channel >60cm Air outlet Deep fo Necessary width 300mm is necessary between 2 outdoor units 300mm M10 bolt 4pieces per unit GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 148
3.6 Cover for E-parts 14 Maintenance board assy 3.7 Main control board 14.1 Maintenance board 3.8 Protection cap 14.2 Handle 3.9 Discharge temp sensor 15 Front panel assy 3.10 Groove clamp 4 15.1 Panel GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 149
Pre-welding assy for distributing 8.1 Suction pipe B for compressor 22.3 capillary Condenser inlet tube shockproof 8.2 Low-pressure switch 22.4 tubule Pre-welding assy for discharge 22.5 Cold out pipe pipe A GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 150
Fan motor capacitor AC contactor Terminal (DJ-75W-5PA) Terminal (DJ-0A-3PA) Protection plate for phase sequence Back mesh Pre-welding assy for compressor suction pipe B Right separating board Pull handle Weld assembly for throttled capillary assy GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 151
The air-returning pipe 18.1 Low-pressure switch 18.2 Base borad for valve assy Base borad for valve 19.1 Stop valve 19.2 Stop valve Compressor assy C-SB303H8A Chassis(No.43 of Commercial) Maintenance panel Median septum GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 152
R410A50Hz Universal Outdoor Series TechnicalManual Outdoor unit 8.4 COU-48HR1 ,COU-60HR1 GD Chigo Heating & Ventilation Equipment Co., Ltd.
1.5. Be sure of no leakage by checking it with leak detector or soap water. 1.6. Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath (fittings), and bind it well with the tapes to prevent leakage. GD Chigo Heating & Ventilation Equipment Co., Ltd.
If it rises, it shows there’s moisture or leakage point. Vacuuming from liquid pipe and gas pipe at the same time. Sketch map of common vacuum dry procedure. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 160
Determinant: Pass if achieving below -755mmHg. If -755mmHg can’t be achieved in 2h, repeat procedure ③ and ④. ⑤. Vacuum placing test ······ 1h ⑥. Sketch map of special vacuum dry procedure GD Chigo Heating & Ventilation Equipment Co., Ltd.
— — Added Refrigerant When 30g/m×(L-5) 65g/m×(L-5) 120g/m×(L-5) Over 5m(One-way) Remark: R (g): Additional refrigerant to be charged L (m): The length of the refrigerant pipe (one-way) D (mm): Liquid side piping GD Chigo Heating & Ventilation Equipment Co., Ltd.
4.2.1. If the pressure at the connection of the drainpipe is negative, it needs to design drainpipe trap. 4.2.2. Every indoor unit needs one drainpipe trap. 4.2.3. A plug should be designed to do cleaning. Plug GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 163
Calculate allowed volume =Total cooling capacity of indoor units(HP)×2 (l/ hr) Allowed volume(lean 1/50) (l/ hr) I.D. (mm) Thick ¢25 Hard PVC ≤14 ¢30 Hard PVC 14< ≤88 ¢40 Hard PVC 88< ≤334 ¢50 Hard PVC 175< ≤334 ¢80 Hard PVC 334< GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 164
Turn off the power and drain the remained water, and then turn on the air conditioner. Note: the drain stuff in the main water receipt plate is for maintenance. Stuff up the drain stuff to prevent water leakage. GD Chigo Heating & Ventilation Equipment Co., Ltd.
5.2.2. Insulation for non-jointing parts and non-connection parts wrong right Gas pipe and liquid pipe should Insulate the gas pipe Insulate the gas pipe and not be put together to insulate (cooling only) liquid pipe GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 166
5.4.2 The gas and liquid pipe should be heat insulated individually, the connecting part should be heat insulated individually. 5.4.3 Use the attached heat-insulation material to insulate the pipe connections (pipes’ tie-in ,expand nut ) of the indoor unit GD Chigo Heating & Ventilation Equipment Co., Ltd.
Whether there is vibration or abnormal noise during operation. Whether the generated wind, noise, or condensed of by the air conditioner have influenced your neighborhood. Whether any of the refrigerant is leaked. GD Chigo Heating & Ventilation Equipment Co., Ltd.
If the signal is received correctly, the air conditioner will issue a "beep" prompt. If the remote controller is not available, please replace the new battery and try again. But if the problem persists, please contact the seller or our authorized service center. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 170
ECON. means cleaning. means electric heating. means address. means lock. means lack of electricity. • Reservation function: means Auto Config. means power saving. means healthy. means new wind. means intelligence. means lamplight. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 171
When pressing this key in dehumidification and fan mode, the temperature will not change. ② In the clock setting state (the clock icon will flicker to show the prompt), this key is used to set the clock time. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 172
TURBO key will not work in automatic mode, dehumidification mode and fan mode. ② Pressing this key in the cooling or heating mode, the TURBO mode switches between opening and GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 173
3 seconds, and recover the clock before the adjustment. (15) Lock ① There is no lock by default. Pressing this key, the lock function switches between opening and GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 174
1)If the air conditioner is unable to receive the signal from the wire controller, or the LCD of wire controller is blurred, it means that the battery is depleted and needs to be replaced. GD Chigo Heating & Ventilation Equipment Co., Ltd.