Control characteristic
The control characteristic is established by the maximum value of the dimensions to
be controlled and the key values of the set point. Using these key values, the linear
control characteristic may be set as desired.
Each controller (e.g. temperature controller) whose output signal lies within the
range 0-20mA / 0-5V / 0-10V, can easily be adapted to the Power Controller.
Control types
Voltage control U
, U
2
rms
Current control I
, I
2
rms
rms
Precision of control
Voltage
± 3 %
Current
± 1,5%
both with reference to the end value
Limitations
Current limitation I
rms
Voltage limit
U
rms
Power limit
P (H RLP)
Relay outputs
Change-over contact, contactor material: AgSn02 / Au plated
The relay can be used for weak load circuits (Π5V 20mA),
but not after a prior load with 230V a.c.
Max. values: 250V 6A 180W, 1500VA
Insulation strength 4kV / 8mm
Ambient temperature
35°C external cooling (F model with integrated ventilator)
45°C self air cooling
At higher temperatures it is possible to operate with reduced type current:
Temperature range up to 55°C: type current -2% / °C
Connector data
Connector U1,W1,U2,W2 Earthing screw
8A
Screw plug-in terminal
16 / 30A
Bracket / M4
45A
M 6
60 / 100A
M 6
130 / 170A
M 8
280A
M 10
With UL applications only use 60°/75° copper conductors!
= standard setting
rms
Thyro-Tool
Thyro-Tool
Thyro-Tool
Bracket / M4
Bracket / M4
M 6
M 6
M 10
M 10
Bus
R203
Bus
Bus
Conductor cross sect.
max. 4mm
2
max. 6mm
2
max. 50mm
max. 50mm
95 / 120mm
150 / 185mm
2
2
2
2
99