Tab. 2d Load Monitoring - AEG THYRO-A Operating Instructions Manual

Thyristor power controller.
Hide thumbs

Advertisement

For Thyro-A 2A (load with joint neutral point without N conductor) the setting for
load monitoring can be made according to the table below:
e.g.
I
load nom.
parallel
/
load
I
type contr.
resistances
Number
1
100%
1
80%
1
60%
-
-

Tab. 2d Load monitoring

Value deviations can be converted by percentage. The set monitoring value must
lie "in the middle" between the nominal load current value and the value after
outage.
NOTE
Settings above 90% and below 10% are not practical. If low load cur-
rents are required, check if a controller with a lower type current can
be used.
In the VAR operating mode monitoring with large trigger delay angles
C
Œ 140°el. is locked.
82
load with joint neutral point without N
Resistance
Recommended
increase
setting
in case of fault
for poti
(L2)
R205
90.0%
72.0%
(54%)
-
-
Thyro-A 2A
X2.9
X2.9 [V]
[0-20mA]
9.0
18.0
7.2
14.4
5.4
10.8
-
-
-
-
ca.
Revo-
lutions
14.0
11.5
9.0
-
-

Advertisement

   Also See for AEG THYRO-A

   Related Manuals for AEG THYRO-A

Comments to this Manuals

Symbols: 0
Latest comments:
  • Leila Tavana Jul 01, 2015 07:39:
    Dear Sir/Madam
    ​This is our pleasured to introduce ourselves -Notash Sanat Sahand Co.- as a trading company active in oil, gas and petrochemi​cal companies in Iran(in piping and instrument field).We have an inquiry for one of our customers as per below. Please check it and send your best price with CPT Tehran terms for us in your soonest attention.​
    Hope to have goon cooperatio​n in soon future.

    T​HYRISTOR CONTROL
    TH​YRO-A 2A 400V
    MODEL : HRL1
    MFR : AEG
    As per attached file
    Qty : 2