The soft start time SST is set at the same time. The also applies to the operating
mode VAR. Depending on AN1 the soft start time has the following value:
AN [1°el] 30
33.7 =33.7 =41.2 =48.7 =56.2 =61.5 =64.5 =67.4 =70.5 =73.5
SST [ms]
0
120
With an ohmic resistance load the poti can be turned to the left limit stop, at
30°el Thyro-A independently switches to a faster pulse operation with
T
= 5 periods without SST.
0
NOTE
In this configuration the terminal X2.7 can be used as an additional
digital "set point value" (24V d.c.). This also enables the controller to
be driven, for example, by a two-position controller.
Analog output (setting guide)
5 V / 10.0mA = 100 °el (Maximum value)
3 V / 6.0mA = 60 °el
1.5V / 3.0mA = 30 °el
1.25V / 2.5mA =
0 °el
3.2.2 Control end set point input
Potentiometer R202 allows the control characteristic to be adapted to the operation.
In central position the factor is = 1, right-hand stop = 2, left-hand stop = 0.
Default setting.
With set point full modulation (20mA, 10V, 5V see 3.1.4) wird U
nal voltage + 10% or I
rms max
type of underlying control.
Analog output (setting guide)
10 V
or
20.0mA
5
V
or.
10.0mA
2.5 V
or.
5.0mA
1.25V
or
2.5mA
Factors 1 result in a shallower characteristic. Full modulation can no longer be
reached. See also Fig. 1 Control characteristic.
140
160
180
200
, i.e. nominal current is reached, depending on the
Factor
=
2
=
1
=
0.5
=
0.25
220
260
300
400
, i.e. nomi-
rms max
Control end
20 V
or
40mA (theor.)
10 V
or
20mA
5 V
or
10mA
2.5V
or
5mA
600