Overloads On The Ups - Riello 700VA User Manual

Table of Contents

Advertisement

Table 1
Battery level
0%~20%
20%~40%
40%~60%
60%~80%
80%~100%
Table 2
Input Voltage
190V~200V
200V~230V
230V~250V
250V~260V
>260V
Table 3
Load level
0~5%
5~25%
25%~50%
50%~75%
75%~102%
>102%
LED on with steady light
LED with flashing light on (1 flash per second)
O
VERLOADS ON THE
The following table shows how the UPS reacts when mains and battery overloads occur and indicates the time
that the UPS will remain powered.
OVERLOAD LEVEL
102% < Load ≤ 109%
110% <= Load ≤ 130%
130% < Load ≤ 150%
Load > 150%
Short circuit
1
2
1
2
25
50
UPS
LOAD POWER TIMES
Switches to bypass after 30 min
Switches to bypass after 30 sec
Switches to bypass after 10 sec
Switches to bypass after 0.5 sec
Immediate shutdown
I
NSTALLATION AND
Battery LED bar
3
Battery LED bar
3
Load LED bar
75
(off mains)
4
4
100
LOAD POWER TIME
(off battery)
Shutdown after 30 min (if battery
back up time allows)
Shutdown after 30 sec
Shutdown after 10 sec
Shutdown after 0.5 sec
Immediate shutdown
U
SE
5
5
!
49