A5ACV 100 / 135 / 210CR
Do not allow water to remain in the water pipes if the unit is not operating for a long period.
Water must be drained out if the unit is not running during winter. Failing to do so would cause the pipe
to crack.
Do not drink the chilled water in the unit.

ELECTRICAL AND WIRING

Refer to the wiring diagram provided on the unit when making electrical wiring.
Do not ground any electrical equipment to the water piping.
Install an external isolator switch (if it is not provided) to prevent electrical shock.

RECOMMENDED FUSE AND CABLE SIZES

Model
Voltage Range**
Recommended Fuse*
Power Supply Cable Size*
Number of Conductor
Interconnection Cable Size*
Model
Voltage Range**
Recommended Fuse*
Power Supply Cable Size*
Number of Conductor
Interconnection Cable Size*
IMPORTANT :
* The figures shown in the table are for information purpose only. They should be checked and
selected to comply with the local/national codes of regulations. This is also subjected to the type of
installation and conductors used.
** The appropriate voltage range should be checked with label data on the unit.
All field wiring must be installed in accordance with the national wiring regulation.
All the terminals and connections must be tightened. Improper connection and fastenings could
cause electric shock, short circuit and fire.
Ensure that the rated voltage of the unit corresponds to that of the name plate before
commencing wiring work according to the wiring diagram.
The unit mus be GROUNDED to prevent possible hazards due to insulation failure.
All electrical wiring must not touch the refrigerant piping, compressor, pump, fan motor or any
moving parts of the fan motors.
Do not operate the chiller with wet hands. It would result in electric shock.
Do not use fuse of different amperage than stated. Using wire etc. to replace a fuse could cause
equipment damage or fire.
PRESSURE GAUGE
GATE
GATE
VALVE
VALVE
GATE
BALANCING
THERMOMETER
VALVE
VALVE
FLEXIBLE
GATE
BALANCING
THERMOMETER
VALVE
VALVE
FLEXIBLE
!
CAUTION
A5ACV30CR
230/1/50
A
36
2
mm
10
3
2
mm
1.5
A5ACV100CR
415/3/50
A
40
2
mm
10
5
2
mm
1.5
!
CAUTION
46
AIRVENT (INSTALL
HIGHEST POSITION)
PRESSURE
DIFFERENTIAL
GATE
VALVE
VALVE
STRAINER
GATE VALVE
CHECK
(LOWER POSITION
VALVE
FOR DRAINAGE)
MAKE UP
VALVE
A5ACV55CR
A5ACV75CR
415/3/50
415/3/50
25
36
10
10
5
5
1.5
1.5
A5ACV135CR
A5ACV210CR
415/3/50
415/3/50
60
100
10
10
5
5
1.5
1.5
FAN COIL UNIT/AIR HANDLING UNIT
Figure 2