Air-cooled chiller r410a inverter series
Table of Contents

Advertisement

COOL MODE ANTIFREEZE
A1
Antifreeze heater set-point
A2
Antifreeze heater differential
A3
Antifreeze sensor select
0=Leaving water, 1=Entering water
A4
Antifreeze alarm set-point
A5
Antifreeze alarm differential
ALARM AND CONTACT
P1
Flow switch confirmation time
P2
Flow switch alarm delay at pump start
P3
Low pressure alarm delay at compressor start up
P4
Comp overload alarm reset type
0=Manual reset, 1=Auto reset
P5
High pressure alarm reset type
0=Manual reset, 1=Auto reset
P6
Low pressure alarm reset
0=Manual reset, 1=Auto reset
P7
Fan overload alarm reset type
0=Manual reset, 1=Auto reset
P8
Pump overload alarm reset type
0=Manual reset, 1=Auto reset
P9
Flow switch alarm reset type
0=Manual reset, 1=Auto reset
P10
Auxiliary alarm reset type
0=Manual reset, 1=Auto reset
P11
Antifreeze alarm reset type
0=Manual reset, 1=Auto reset
P12
Comp overload contact type
0=Normally close(NC) 1=Normally open(NO)
P13
High pressure contact type
0=Normally close(NC) 1=Normally open(NO)
P14
Low pressure contact type
0=Normally close(NC) 1=Normally open(NO)
P15
Fan overload contact type
0=Normally close(NC) 1=Normally open(NO)
P16
Pump overload contact type
0=Normally close(NC) 1=Normally open(NO)
P17
Flow switch contact type
0=Normally close(NC) 1=Normally open(NO)
P18
External alarm contact type
0=Normally close(NC) 1=Normally open(NO)
P19
Defrost end contact type
0=Normally close(NC) 1=Normally open(NO)
INVERTER
V1
Compressor frequency
V2
EXV Opening
V3
Compressor manual setting
0= disable 1= enable
V4
EXV Manual setting
0=disable
1= enable
V5
Defrost Mode
0= disable 1= enable
Unit
Default
°C (F)
5 (41)
°C (F)
2 (3.6)
Flag
0
(leaving)
°C (F)
3 (37)
°C (F)
2 (3.6)
Unit
Default
sec
5
sec
120
sec
30
Flag
0
(manual)
Flag
1
(auto)
Flag
1
(auto)
Flag
1
(auto)
Flag
0
(manual)
Flag
0
(manual)
Flag
1
(auto)
Flag
1
(auto)
Flag
0
(NC)
Flag
0
(NC)
Flag
0
(NC)
Flag
0
(NC)
Flag
0
(NC)
Flag
0
(NC)
Flag
0
(NC)
Flag
0
(NC)
Unit
Default
Hz
Auto
Flag
Auto
Flag
0(disable)
Flag
0(disable)
Flag
0(disable)
38
Min
Max
Resolution
-40 (-40)
40 (104)
1
0.4 (0.7)
10 (18)
0.1
0
1
1
-40 (-40)
40(104)
1
0.4 (0.7)
10 (18)
0.1
Min
Max
Resolution
0
199
1
0
199
1
0
199
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
Min
Max
Resolution
0
120
1
0
480
1
0
1
1
0
1
1
0
1