Compressor; Condenser Defrost; Cool Mode Antifreeze; Inverter - Acson A5ACV 30 CR User Manual

Air-cooled chiller r410a inverter series
Table of Contents

Advertisement

3) Compressor

C1 Min Run
: 12s
C2 Min Stop
: 240s
C3 2On Interval : 360s
C4 2Cp ON Dly : 15s
C5 P-Cp ON Dly : 60s
C6 Cp-P OFF Dly: 40°C
C7 Cp Cut Off
: 120°C

4) Condenser Defrost

D1 Start Temp
: -3°C
D2 End Temp
: 14°C
D3 Max Dura
: 10m
D4 Interval
: 45m
D5 Dly Bfr Def
: 0s
D6 Dly Aft Def
: 0s

5) Cool Mode Antifreeze

A1 Heater SP
: 5°C
A2 Heater Diff
: 2.0°C
A3 Sensor
: Leave
A4 Alarm SP
: 3°C
A5 Alarm Diff
: 2.0°C

6) Inverter

V1 Cp Freq
: 100Hz
V2 EXV
: 180
V3 Cp Manual
: Disable
V4 EXV Manual : Disable
V5 Def Mode
: Disable
7) Alarm and Contact
P1 FS Confirm
: 5s
P2 FS Delay
: 180s
P3 LP Delay
: 30s
P4 CO Reset
: Manual
P5 HP Reset
: Auto
P6 LP Reset
: Auto
P7 FO Reset
: Manual
Please refer to 8. APPENDIX for detail desciption.
P8 RO Reset
: Manual
P9 FS Reset
: Manual
P10 Aux Reset : Manual
P11 A/F Reset
: Manual
P12 CO Contact : Normal
P13 HP Contact : Normal
P14 LP Contact : Normal
28
P15 FO Contact : Normal
P16 PO Contact : Normal
P17 FS Contact : Normal
P18 EA Contact : Normal
P19 DE Contact : Normal

Hide quick links:

Advertisement

Table of Contents
loading