Dummy Loading Unused Circuits; The Eia Interface - Fire-Lite Sensiscan 200 Installation, Operation, And Programming Manual

Expandable multi-zone fire alarm control panel
Hide thumbs Also See for Sensiscan 200:
Table of Contents

Advertisement

4.7K, 1/2-watt Resistor,
An unused notification circuit can be termi-
nated with one dummy-load resistor (illus-
trated above on Terminals 1-4) or with two
jumpers (illustrated above on Terminals 5-8).
Figure 4-2: Dummy-loading of Unused Circuits
EIA-485 Interface
The control panel communicates with the serial annunciator modules of the AFMX and LDM Series
through the EIA–485 interface on the CPU. The EIA terminal block is installed on the lower CPU
board. Maximum distance is 6000 feet. Maximum resistance is 100 ohms.
22
Part # 71245.
EIA-485 (+)
EIA-485 (-)
Figure 4-3: The EIA-485 Interface
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
4.7K, 1/2W Resistor
Part # 71245
If the Municipal Box Output is not to be
used, it must be terminated with a
dummy-load resistor.