Upflow/ horizontal and downflow/ horizontal, gas-fired, direct vent, variable speed inducer, modulating condensing communicating furnaces
Hide thumbs Also See for UHMB060ACV3VA:
Table of Contents

Advertisement

k
ANCHORS
(4 req.)
VENT
3.2"
COMBUSTION
AIR
VENT
CAP
BAYVENT200B
For Canadian applications only, IPEX 196006, IPEX 081216, IPEX 081218,
and IPEX 081219 may be used for horizontal vent terminations.
;
D
E E
V
V
B
L
V
VENT TERMINAL
VENT FITTING MATERIAL – STAINLESS STEEL
Gas and liquid tight single wall metal vent fitting, de-
signed for resistance to corrosive flue condensate such
as Type 29-4C MUST be used throughout.
These fittings and fitting accessories are to be supplied
locally.
18-CD30D1-9
VENT
PLATE
12" MINIMUM
TO OVERHANG
VENT
MAINTAIN 12" MINIMUM CLEARANCE
ABOVE HIGHEST ANTICIPATED SNOW LEVEL
OR GRADE WHICHEVER IS GREATER
HORIZONTAL VENT CLEARANCES
(See clearance tables 11 and 12 on page 24)
CORNER DETAIL
C
V
B
V
V
B
F
B
X AIR SUPPLY INLET
l
COMBUSTION
SCREWS
(4 req.)
BAYAIR30AVENTA
(Side wall)
For Canadian applications only, IPEX 196006, IPEX 081216, IPEX 081218,
and IPEX 081219 may be used for horizontal vent terminations.
INSIDE
G
V
B
V
X
V
J
B
A
AREA WHERE TERMINAL IS NOT PERMITTED
DIRECTION OF STAINLESS STEEL FITTING
All stainless steel fitting must be installed with male
end towards the Furnace.
All horizontal stainless steel sections must be posi-
tioned with the seam on top.
All long horizontal sections must be supported to pre-
vent sagging.
All pipe joints must be fastened and sealed to prevent
escape of combustion products into the building.
Installer's Guide
12" MIN TO
OVERHANG
1" +
1
"
2
AIR
VENT
MAINTAIN 12 IN.
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED SHOW
LEVEL OR GRADE
WHICH EVER IS GREATER
CONCENTRIC VENT
SIDE WALL INSTALLATION
H
I
M
V
X
K
23