Vent Termination Zones - Natural Gas
• ALL VENTING MUST TERMINATE (END) WITHIN ONE OF
THE SHADED AREAS.
• SET STOVE EXHAUST RESTRICTOR TO THE POSITION
THAT CORRESPONDS TO THE VENT TERMINATION AREA
IN THE DIAGRAM ABOVE.
• ALWAYS MAINTAIN THE PROPER CLEARANCES TO
COMBUSTIBLES.
The circled letter designations in the vent diagram correspond
to the Exhaust Restrictor Setting on the stove. First, determine
which vent termination zone is appropriate for your installation
and fuel type, then adjust the restrictor to the corresponding
position as shown in Figure 7, page 9.
Figure 9. Coaxial Vent Termination Window / NG
10
Horizontal and Vertical
Terminations for COAXIAL VENT
Vertical
Termination for
COLINEAR VENT
• VENTING MUST TERMI-
NATE (END) WITHIN THE
SHADED AREA.
• Adjust the Exhaust
Restrictor to position B
for any NG colinear
termination.
Figure 10 . Colinear Termination / NG