STATUS
101
Room relative Humidity:
Room Rel. Humidity
Display the Room Relative Humidity if a room humidistat is connected to the
64%RH
humidifier.
STATUS
104
System demand:
System Demand
Display the humidity demand from the system.
64,3%
100% represent a full demand.
STATUS
System Output:
105
System Output
Display the output for each module.
H1: 45,5%
H2: 43,0%
Value is indicated in %. So 50% of a 500 lb/h module would represent 250 lb of
H3: 42,5%
steam per hour output.
H4: 41,0%
STATUS
Hours before drain:
106
Hours before drain
Display the remaining time before the next automatic flush for each module.
H1: 4H
H2: 2H
The automatic flush of the evaporation chamber is fully programmable. Please refer
H3: 3H
to display # 301 for more details.
H4: 1H
STATUS
107
Running Hours:
Running Hours
Display the number of hours of operation since the last servicing for each module.
H1: 2H
H2: 2H
Value is indicated in hours. This counter can be reset after each servicing.
H3: 3H
H4: 1H
Total Running Hours:
STATUS
108
Total Running Hours
Display the total number of hours of operation for each module since the original
H1: 40H
start-up.
H2: 25H
H3: 22H
This counter cannot be reset.
H4: 20H
STATUS
Water level:
109
Water level
Display the reading of water level electronic probe for each module.
H1: 98%
H2: 99%
Value is indicated in %, 100% indicate that the evaporation chamber is full of water.
H3: 101%
During normal operation, the value can fluctuate between 95% and 105%.
H4: 98%
STATUS
Water Temperature:
110
Water Temperature
Display the water temperature inside the evaporation chamber for each module.
H1: 32°C
H2: 35°C
Value is indicated in
H3: 31°C
(100˚C).
H4: 29°C
STATUS
Chimney Temperature:
111
Chimney Temperature
Display the Flue gases temperature for each module.
H1: 41°C
H2: 45°C
Value is indicated in
H3: 60°C
410˚F (210˚C).
H4: 51°C
STATUS
112
Unit Size:
Unit Size
Display total capacity of each module.
H1: 110 lb/Hr
H2: 105 lb/Hr
Value is indicated in lb/h.
H3: 103 lb/Hr
H4: 110 lb/Hr
Description
˚C. During normal operation this temperature should be around 212˚F
˚C. During normal operation this temperature should be lower than