Power Fuse Open Power fuse located on the Slave PCB is open.
Input Volt. Too low
No Water T. Sensor Humidifier does not receive signal from water temperature sensor.
No Chimney T. Sensor Humidifier does not receive signal from flue gases venting temperature sensor.
Water level error Humidifier does not receive signal from water level sensor.
Foaming in the tank
Water Temp. too low
Water Temp. too high
Chim. Temp. too low
Tank cannot fill
Tank cannot refill
Tank cannot drain
Burner Fan Defect Burner fan is running too low or too fast than the required humidity output.
Burner Locked Gas burner did not light-up after 3 tentative. Gas burner should be verified.
For information on troubleshooting please refer to the Service and Troubleshooting guide supplied.
No alarm should be reset prior to identify and rectify the root cause of the fault.
Please refer to the trouble shooting guide for help to identify and resolve potential
problems.
When an alarm is indicated by the LCD display, the Red LED Alarm will flash.
Normal operation of the humidifier is altered.
To manually reset alarm, press simultaneously
Replacing this fuse will automatically reset this alarm.
Power supply voltage is too low for proper operation of the humidifier.
Verify power supply voltage level and take necessary action. Proper voltage level will
reset this alarm.
After communication re-establish, the alarm will have to be reset manually.
After communication re-establish, this alarm will have to be reset manually.
After communication re-establish, this alarm will have to be reset manually.
Humidifier is detecting foam in the tank and has performed a de-foaming cycle.
This alarm will be automatically reset when foaming condition are over.
Water temperature is below the pre-set minimum value; humidifier will fire-up the
burner to heat-up the water.
This alarm will reset automatically when water temperature will reach the proper
value.
Water temperature is above the pre-set maximum value; humidifier will shut-off and
cool down until water temperature reaches a proper value.
This alarm will reset automatically when water temperature will reach the proper
value.
Flue gases temperature is above the pre-set maximum value; humidifier will shut-off
and cool down until flue gases temperature reaches a proper value.
This alarm will reset automatically when flue gases temperature will reach the proper
value.
Water filling of the evaporation chamber is taking more time than the expected
maximum time. Humidifier will not fire-up until proper water level is reached.
This alarm will reset automatically when water will reach the proper level.
The time period between two refilling of the evaporation chamber is longer than
expected. Investigation to define the cause of this fault is necessary.
This alarm will have to be reset manually.
Water draining of the evaporation chamber is taking more time than the expected
maximum time.
This alarm will reset automatically when water will be totally evacuated.
This alarm will have to be reset manually.
This alarm will have to be reset manually.
SKG3 Steam Humidifier
&
39

List of Alarms

buttons for 3 seconds.