Stage 5 - Water Drain Connection - Neptronic SKG3 Series Installation Instructions Manual

Gas fired
Table of Contents

Advertisement

!
Water Drain installation should conform to local codes and regulations.
Any installation work must be carried out by suitably qualified personnel.
Water Drain
Water Drain temperature: 140˚F (+60˚C)
Specification
Water Drain
Water drain outlet connection should be connected to drain pipe of sufficient size.
Installation
We recommend the use of Ø1 ½'' (38mm) minimum standard copper hydraulic
pipes.
Minimum water drain pipe gradient should be ¼'' (1.5mm) in 40'' (1m) horizontal run.
No drain trap is required.
SKG3
Stage 5 – Water Drain Connection
Model
SKG3-
110 to 810
1½'' (38)
2 ¾'' (70)
(Fig. 24)
dimensions in bracket are in mm
18
SKG3 Steam Humidifier
Water Drain Outlet
Connection size
1 ½''
(38mm)
Ø 1½'' (38)
minimum