Fault And Warning List; Troubleshooting - Nortec GS 100 Installation, User & Maintenance Manual

Gs series gas steam humidifier
Hide thumbs Also See for GS 100:
Table of Contents

Advertisement

GSTC fault
GSP fault code
displayed
FAULT
NO BURNERS
AVAILIBLE
FAULT
AIR PROVING
SWITCH X OPEN
WITH
BLOWERS ACTIVE
FAULT
AIR PROVING
SWITCH X
CLOSED WITH
BLOWERS
INACTIVE
FAULT
BLOWER X
RPM HIGH
FAULT
BLOWER X
RPM LOW
FAULT
BLOWER X
NOT OPERATIONAL
FAULT
ILLEGAL GAS
VALVE
BURNER X
FAULT LIST
displayed
NBF
Once the GS controller detects an ignition
module fail, it will index to the next available
ignition module. If all ignition modules have
failed or there are none available (in the case of
a 100 unit) this fault will be generated
AOF-X
On startup after 3 tries if the AP switch does
not close within the proving period, this fault
ACF-X
On initial startup if any of the A/P switches are
closed this fault will be generated.
BHF-X
If the blower RPM is above the RPM tolerance
for more than 10 seconds, this fault is
generated and the humidifier stops.
BLF-X
If the blower RPM is below the RPM tolerance
for more than 10 seconds, this fault is
generated and the humidifier stops
BNF-X
On startup, if the blower RPM does not exceed
500 RPM within 5 seconds or if during
operation, the RPM drops below 500 RPM for
more than 5 seconds this fault is generated
GVF-X
If the controller detects that a gas valve has
activated at a time it should not this fault is
Description of fault
will be generated
Generated.
- 60 -

Troubleshooting

-Check red LED's on all modules for
flashing fault code
-Ensure there is gas supply to the
humidifier
-Ensure that the burners have not been
disabled in the software
-Consult factory
-Check that blue hoses on the Air
Proving switch have not come loose.
-Check that wires on the Air Proving
switch are on the N/O contacts
-If available, swap Air Proving switch
with another and see if the fault follows
the air proving switch, if so, replace
switch
-Consult factory
-Ensure that wiring on the air proving
switch is on the N/O contacts
-Ensure that there is no continuity
between the switch with the wires off,
if so replace switch
-Ensure that there is not a strong
positive pressure in the room holding
the switch closed
-Consult factory
-Check wiring to lead blower and
ensure a good connection.
-Check lead blower for any restrictions
by testing it in the diagnostics screen.
-Consult factory
-Check wiring to blower X and ensure
a good connection.
-Check blower X for any restrictions by
testing it in the diagnostics screen.
-Consult factory
-Ensure there is power to the blower
and that all wires are making a proper
connection.
-Consult factory
-Ensure that the ignition module is not
miswired or that the module is not
faulty by swapping it with a known
good one. If the problem follows the
ignition module, replace the module
-Consult factory