Mandatory Maintenance Schedule - Nortec GS 100 Installation, User & Maintenance Manual

Gs series gas steam humidifier
Hide thumbs Also See for GS 100:
Table of Contents

Advertisement

30 DAYS
PARTS
after initial
start-up
Hot Surface
Ignitor
Flame Sensor
Gas Burner
Drain Lines
Tank
X
Float Chamber
X
Fill Lines
X
Drain Lines
X
Gas Venting
X
Direct Vent
H/L Stack Sensor
X

MANDATORY MAINTENANCE SCHEDULE

END OF
MID
SEASON
X
- Check that Flame Sensor is straight.
X
- Clean sensor with fine steel wool.
- Remove from the unit and clean with compressed
X
NOTE: It is recommended to replace the burner
gasket each time a burner is removed.
X
- Switch to drain and make sure water flows freely.
- Adjust blow down time when required. Check that
scale has not accumulated above 2".
X
X
X
X
X
X
- Inspect for leaks at the drain pump, fill cup and
X
X
- Inspect for leaks. Ensure terminal cap is clear and
X
X
any condensation produced flows to condensate
traps. Flue temp should be between 350-400ºF.
X
X
- Inspect for leaks. Ensure intake terminal is clear.
- Visual check that sensor is intact, wired and
X
X
WHAT NEEDS TO BE DONE?
REGULAR MAINTENANCE
- Check for continuity.
air from outside matting.
- Clean tank when required.
- Ensure floats move freely.
- Inspect for leaks.
float chamber.
attached to the exhaust.
PREVENTIVE MAINTENANCE
- Replace hot surface ignitor and flame
sensor with replacement kit.
- Drill out tank nipples when required to
ensure nipples are not blocked with scale.
- Clean tank.
- Clean scale from float chamber and hose
connecting to hit.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents