22. ADJUSTMENT AND SAFETY DEVICES

This boiler has been designed in full compliance with European reference standards and, in particular, it is fitted with the following:
Air pressure switch (model 140 Fi - 240 Fi - 280 Fi - 320 Fi)
This device (17 - figure 20) only allows the burner to ignite if the exhaust flue duct is in perfect working order.
In the event of one or more of the following faults:
• flue terminal obstructed
• venturi tubes obstructed
• fan blocked
• venturi tube connection - pressure switch tripped
The boiler remains on standby and error code E03 is displayed (see table in section 9).
Fumes thermostat (model 240 i - 280 i)
This device (15 - figure 21), the sensor of which is positioned to the left of the fumes hood, interrupts the flow of gas to the main burner if the flue is
obstructed and/or there is no draught.
In these conditions the boiler shuts down and displays error code E03 (section 9).
To restart immediately, after having removed the cause of intervention, see section 9.
It is forbidden to disable this safety device
Safety thermostat
Thanks to a sensor placed on the heating delivery line, the thermostat interrupts the flow of gas to the burner if the water in the primary circuit
overheats. In these conditions, the boiler is blocked and only after the fault has been eliminated can it be ignited again (See section 9).
It is forbidden to disable this safety device
Flame ionisation detector
The flame sensing electrode, located on the right-hand side of the burner, guarantees safety of operation in case of gas failure or incomplete ignition
of the burner.
In these conditions, the boiler is blocked after 3 ignition attempts.
To re-establish normal operating conditions, see section 9.
Hydraulic pressure switch
This device allows the main burner to be ignited only if system pressure is higher than 0.5 bars.
Pump overrun for heating circuit
The electronically-controlled pump post-circulation function lasts 3 minutes (F17 – section 21) and is enabled, in the heating mode, if the ambient
thermostat causes the burner to go out.
Post-circulation of the DHW circuit pump
The pump post-circulation, which is obtained electronically, has a duration of 30 seconds and is activated at the end of operation of the DHW
pump.
Frost protection device (heating and DHW systems)
The electronic boiler management system includes a "frost protection" function for the heating system which, when delivery temperature falls below
5°C, operates the burner until a delivery temperature of 30°C is reached.
Lack of water circulation in the primary circuit (probably pump blocked or presence of air)
If there is insufficient or no water circulating in the primary circuit, the boiler blocks and the error code 25E is shown on the display (section 9).
Anti-block pump function
If no heat demand is received for 24 consecutive hours, the pump will automatically start and operate for 10 seconds.
This function is operative when the boiler is powered.
Three-way valve anti-blockage function
If no heat demand is received for a period of 24 hours, the three-way valve performs a complete switching cycle. This function is operative when the
boiler is powered.
Hydraulic safety valve (heating circuit)
This device is set to 3 bar and is used for the heating circuit.
Connect the safety valve to a drain tap. Do not use it to drain the heating circuit.
Anti-legionellosis function
The anti-legionellosis function is NOT active.
To activate the function, set the parameter F21=01 (as described in section 21). When the function is active, at intervals of one week the boiler
electronic management brings the water contained inside the boiler to a temperature higher than 60°C (the function is operative only if the water has
never exceeded 60°C in the previous 7 days).
NOTE:
domestic hot water is guaranteed even if the NTC sensor (ref. 5 – figures 19-20) develops a fault. In this case, temperature is controlled
by the delivery sensor.