5.7.4 Assembly steps of AC connector

SolarRiver series inverters are designed for single phase grid. Technical data should comply with the
rule of local public grid.
Model
Cable (Cu)
Micro-Breaker
Micro-breaker should be installed between inverter and grid, and the residual current is 30 mA≤Ifn≤300 mA.
Any load should not be connected with inverter directly.
Impedance of SolarRiver-D inverter AC connector should be less than 2Ω. To ensure anti-islanding
function reliable, wire loss power of PV cable should <1% of normal power. Length between inverter
AC side and grid connecting dot should be less than 150m. Relationship between cable and cable loss
is as following:
18
Table 3 Cable and Micro-breaker rule
SolarRiver
3400TL-D
4mm²
20A
ESC
OK
Input
Output
Figure 13 Incorrect Connections between Load and Inverter
Figure 14 AC Cable Loss
SolarRiver
SolarRiver
4000TL-D
4500TL-D
4mm²
4mm²
20A
25A
SolarRiver
SolarRiver
5000TL-D
5200TL-D
6mm²
6mm²
32A
32A