ACV Prestige Solo 60 Installation And Maintenance Manual page 68

Table of Contents

Advertisement

Start-Up Procedures
Test High Temperature Limit
c
The high temperature limit can be temporarily
lowered from 210ºF [99ºC] to 102ºF [39ºC] for
testing.
1. Press the round INSTALLER button.
Reference Fig. 31, page 41.
2. Enter the installer access code "054" by
using LEFT and RIGHT buttons to select
a digit and the UP and DOWN buttons to
change the digit. Press the OK button to
enter the access code.
3. Press the OK button while CH & DHW
Settings icon
is highlighted.
4. Press the DOWN button to highlight the
Boiler Settings icon
button.
5. Press the DOWN button to highlight
Lockout Temperature then press the OK
button.
6. Press the UP button to highlight 102ºF
[39ºC] then press the OK button.
7. Press the DOWN button twice to highlight
the Home Screen icon
OK button.
then press the OK
then press the
62
8. Initiate a CH or DHW call and confirm that
a High Boiler Temperature lockout occurs
once the supply temperature reaches 102ºF
[39ºC].
9. Press any ARROW button to return to the
Home Screen.
10. Press the round INSTALLER button.
11. Press the OK button while the CH & DHW
Settings icon
is highlighted.
12. Press the DOWN button to highlight the
Boiler Settings icon
button.
13. Press the DOWN button to highlight
Lockout Temperature, then press the OK
button.
14. Press the DOWN button to highlight 210ºF
[99ºC] then press the OK button.
15. Press the DOWN button twice to highlight
the Home Screen icon
OK button.
16. Press the OK button to reset the lockout
and return the unit to service.
then press the OK
then press the