INSTALLATION
BOILER ROOM
Important
• Never obstruct the ventilation.
• Do not store inflammable products in the boiler room.
• Avoid storing corrosive products such as paint, solvents, chlorine,
salt, soap or other cleaning products near the boiler.
Accessibility
The boiler room should be big enough to allow easy access to the
boiler. Minimum clearances around the boiler (mm):
- to the front
500
- to the rear
150
- to the sides
100
- above
700
Ventilation
The boiler room must have both low and high level ventilation
.
Fig. 3)
By way of information, the table below gives the minimum
ventilation requirements according to Belgian regulations.
The user must ensure that his boiler room ventilation complies
with local regulations.
Ventilation
Fresh air supply min.
m
3
/h
High level ventilation (A)
dm
2
Low level ventilation (B)
dm
2
Draught stabiliser (C)
Ø
N.B.:
The figures for (B) and (C) only apply to type B23 connectors.
Base
The base on which the boiler will be mounted must be made from
non-combustible materials.

CHIMNEY CONNECTIONS

IMPORTANT
The boiler must be installed by a qualified engineer in
accordance with the local standards and codes of
practice.
The diameter of the chimney must not be less than the
diameter of the boiler's chimney reducer.
6
(see
SV - MV / 35
SV - MV / 50
63
90
1.5
1.5
1.5
2
80
100
Chimney connector type: B23
The chimney must be connected to the boiler by means of a metal
pipe rising at an angle from the boiler to the chimney.
A chimney connection is required.
A. High level ventilation
B. Low level ventilation
C. Draught stabiliser
D. Flame inspection window
E. Height of lined chimney
F. Chimney diameter
A
B
Fig. 3: Boiler ventilation and chimney connection type B23
Chimney
E = 5 m Ø min. F
mm
E = 10 m Ø min. F
mm
E = 15 m Ø min. F
mm
Important note:
The above table is shown by way of indication only as
regulations vary from country to country.
The high efficiency of our boilers means that the flue
gases exit at low temperature. The attendant risk of
condensation may cause damage to some chimneys.
To avoid this risk we strongly advise that you line the
chimney.
Please contact your installer for further information
about chimney lining.
CHIMNEY CONNECTORS TYPE: C XX
• C 13 (x): Concentric / parallel connector with horizontal terminal.
• C 33 (x): Concentric / parallel connector with vertical terminal.
• C 43 (x): Concentric / parallel connector for several boilers in a
common chimney.
• C 53 (x): Parallel chimney connector with air intake and flue gas
outlet in different pressure zones (different locations).
• C 63 (x): Connector for connection to an approved discharge system
(Netherlands, Germany and Luxembourg only)
(Fig.3)
F
C
D
SV - MV / 35
SV - MV / 50
213
236
179
199
162
179
(Figs. 4, 5 and 6)
.

Advertisement

Table of Contents
loading

Summary of Contents for ACV SV - 35

  • Page 1: Chimney Connections

    INSTALLATION BOILER ROOM Chimney connector type: B23 (Fig.3) The chimney must be connected to the boiler by means of a metal pipe rising at an angle from the boiler to the chimney. Important A chimney connection is required. • Never obstruct the ventilation. •...
  • Page 2: Installation

    Horizontal terminal 3.53 Condensation drain 2.06 1.53 This table is based on the equipment offered by ACV and connot be applied generally. Sample calculation The diagram below consists of the Fig. 4: Chimney connectors type C xx following parts (Ø 80 mm) : •...
  • Page 3: Connecting The Heating System

    Safety group • A pump; The safety group of the water tank must be approved by ACV and • A 3-way manual valve. This valve calibrated to 7 bar; the group's valve discharge must be connected can be motorised if required;...
  • Page 4: Connection To The Gas Supply

    INSTALLATION Optional accessories Circuit diagram of ACV control kits B2. Temperature sensor Safety group Ø 3/4” B9. Outdoor sensor B5. Analog/digital room sensor Pressure reducing valve Ø 3/4” P1. Pump Y1/Y2/N. Servomotor (SQK 349) Thermostatic mixer Ø 3/4” bl. Blue N...
  • Page 5: Electrical Connections

    INSTALLATION ELECTRICAL CONNECTIONS Delta performance SV (Fig. 10) Principle of supply 1 2 3 4 5 6 7 8 9 10 11 12 The boiler operates on a single-phase supply of 230 V/50 Hz. You L1 N should install a control box with main switch and 6 A fuses externally to the boiler to allow the boiler to be isolated from the supply for servicing and repairs.
  • Page 6 INSTALLATION Delta performance SV (Fig. 11) 9 10 11 12 Start Max. Min. Pri 230V - 50/60 Hz SEC 18V - 2,0 VA Typ EI 30/15,5 BV 030-7308.OS 1 2 3 4 BG 2000-MV Delta Performance MV 1 2 3 4 5 230 V-50Hz 230V-50Hz...
  • Page 7: Burner Characteristics

    Gas burner ACV BG 2000-MV Prohibited in Belgium. The ACV BG 2000-MV burner is based on the technology of the ACV BG 2000-SV burner but offers the benefits of a modulating burner. Conversion kit supplied with the boiler comprises: The burner's output is constantly adjusted to suit the fluctuating - Orifice(s).
  • Page 8 BURNER CHARACTERISTICS BURNER BG 2000-SV Burner chamber plate Flame inspection window Ignition cable Ionisation cable Control/monitoring relay BURNER BG 2000-MV Burner chamber plate Flame inspection window Box containing the p.c.b. Ignition cable Control/monitoring relay Ionisation cable PWM connector...
  • Page 9 BURNER CHARACTERISTICS OPERATING PRINCIPLE OF THE BURNER AIR/GAS mixture control 1. Air (Fig. 12) 2. Gas The fan draws air in across the venturi. This creates a vacuum P1 at 3. Venturi the venturi neck. The gas valve regulator now reacts to maintain a 4.
  • Page 10: Setting Parameters

    BURNER CHARACTERISTICS SETTING PARAMETERS TYPE SV/35 SV/50 MV/35 MV/50 Input 34.9 10 / 34.9 15 / 50 Nominal output 46.7 9.5 / 32 14.5 / 46.7 Combustion efficiency - natural gas 92.9 93.5 96.4 / 92.9 97 / 93.5 Offset mbar - 0.4 - 0.4...
  • Page 11 If the fan of a BG 2000-MV burner is replaced, the fan's speed is controlled directly by the PWM connector which connects the fan to the p.c.b. The potentiometers on the p.c.b. (Start, Min. and Max.) must be adjusted by an engineer approved by ACV.
  • Page 12: Burner Maintenance

    BURNER CHARACTERISTICS ELECTRODE DISTANCE AND GAP BURNER MAINTENANCE (refer to Fig. 20) • Distance between ionisation electrode and tube: 1. After dismantling the burner, check the condition of the ignition X = 10 to 15 mm (refer to Fig. 17) electrode (1) and ionisation electrode (2), the insulation (3) and •...
  • Page 13: Fault Table

    BURNER CHARACTERISTICS FAULT TABLE Corrective measures Problems Condensation in the chimney: Smell of flue gas: Insufficient heating: The burner switches to safety mode after lighting: Noisy pump: Not enough hot water: Pump not running: Burner fails to light: The manual reset high limit thermostat is tripped: Reasons Chimney is cold and/or not lined Boiler T°...
  • Page 14 Replace the gas valve and set it up according to the setting parameters Replace the p.c.b. Replace the boiler thermostat/potentiometer Fill and vent the system and the boiler Insert the NTC sensor in the pocket correctly ACV provides details of training courses on the maintenance of BG 2000 burners...