Installing Vent/Combustion Air & Condensate Drain
NOTI E
The drain line materials must be an
approved material by the authority hav-
ing jurisdiction.
authority, PVC and CPVC piping must
comply with ASTM D1785 or D2845.
The cement and primer used on the pip-
ing must comply with ASME D2564 or
F493. For installations in Canada, use
CSA or ULC certified PVC or CPVC
pipe, fittings and cement/primer.
8. Continue the pipe from the drain assembly
to a floor drain or condensate pump.
NOTI E
When selecting and installing a conden-
sate pump, ensure the pump is approved
for use with condensing boilers and fur-
naces. The pump should be equipped
with an overflow switch to prevent prop-
erty damage from potential condensate
spillage.
Place the Metal Washer
and (2) Rubber Gaskets
in this Order for Proper
Fig. 14: Condensate Drain Assembly
In absence of such
Retaining Nut
Seal.
Plastic Ball
(Not shown)
Condensate
Drain Assembly
9. The PRESTIGE Solo will typically produce
a condensate that is considered slightly
acidic with a pH content below 3.0. Install
a neutralizing filter if required by authority
having jurisdiction.
CAUTION
The condensate drain must remain filled
and unobstructed and allow unrestricted
flow of condensate. The condensate
should not be subject to conditions
where freezing could occur. If the con-
densate is subjected to freezing or
becomes obstructed , it can leak, result-
ing in potential water damage to the boil-
er and surrounding area.
Fill Plug
with Vaccum
Break Port
Compression
Nut with Rubber Seal
Flexible Tubing
CPVC Piping
25
(or 3/4 PVC/
to Drain)