10-5. Manual address setting using the remote controller

Procedure when setting indoor units' addresses first under the condition that indoor wiring has been completed
and outdoor wiring has not been started (manual setting using the remote controller)
Wiring example of 2 refrigerant lines
Refrigerant line 1
Outdoor
unit
Indoor unit 1
Remote
controller
Line (system) address
Indoor unit address
Group address
Header unit
In the example above, disconnect the remote controller connections between the indoor units
and connect a wired remote controller to the target unit directly before address setting.
<RBC-AMT
>
Pair the indoor unit to set and the remote controller one-to-one.
Turn on the power.
1
Push and hold the
LCD starts flashing.
<Line (system) address>
2
Push the TEMP.
3
Push the TIME
(Match the address with the address on the interface P.C. board of the header outdoor unit in the same refrigerant
line.)
4
Push
button.
(It is OK if the display turns on.)
Indoor unit 2
Indoor unit 3
1
1
1
2
1
2
Follower unit
SET DATA
TEMP.
2, 5, 8
TIMER SET
11
FILTER
RESET
TEST
SET
1
,
and
buttons at the same time for more than 4 seconds.
/
buttons repeatedly to set the CODE No. to
/
buttons repeatedly to set a system address.
Refrigerant line 2
Outdoor
unit
Indoor unit 1
1
2
3
1
2
2
Follower unit
Follower unit
Code No.
ON / OFF
3, 6, 9
FAN
MODE
4, 7, 10
TIME
SAVE
VENT
CL
SWING/FIX
UNIT LOUVER
- 91 -
Indoor unit 2
2
2
2
Follower unit
12 12 12 12 12
.