) . System Control (for Mr. SLIM)
VARIETY OF SYSTEM FUNCTION
System Name
System Diagram
Indoor unit
A.Remote control-
ler operation
(Standard)
B.Remote control-
ler operation
Use of 2 con-
trollers enables
operation of the air
conditioner both
* One of the wired remote con-
from a distance
trollers must be set as a sub
and nearby.
remote controller.
C.Group control
operation
Use of 1 remote
controller to con-
Remote
trol multiple air
Controller
conditioners with
the same settings
simultaneously.
* Outdoor unit`s re-
frigerant address
needs to be set.
D.Remote/local
combined control
operation
Allows start/stop
Remote Controller
of the air condi-
Remote operating panel
tioner from a dis-
tance, and prohib-
its/permits start/
stop from remote
controllers.
E.Operation by
external signal
F.Control by external
signal and remote
display
Remote Controller
Enables you to
display the op-
Remote display panel
eration state and
(operation, error)
control start/stop
from a distance.
58
There are 2 types of remote controllers: wired type
and wireless type.
Simultaneous twin, triple and quad units are counted
as 1 unit, and the indoor units are started or stopped
simultaneously.
Outdoor
Remote
unit
Controller
Up to 2 remote controllers can be connected to
Indoor
one group.
unit
Simultaneous twin, triple and quad units are counted
as 1 unit.
Remote
Operation control by the latest command (last en-
Controller
tered priority)
Wired and wireless remote controllers can be com-
bined as a pair.
One group can consist of up to 16 indoor units, and
Indoor
they can be started sequentially by connecting the
unit
remote controller to them and assigning an address
Outdoor
unit
to each outdoor unit.
Simultaneous twin , triple and quad units are counted
as 1 unit.
All the units belonging to the same group are oper-
ated in the same mode, but thermostats can be
turned ON/OFF individually for each outdoor unit.
Up to 2 remote controllers can be connected.
All the air conditioners can be turned ON/OFF collectively
from a distance.
Relay box
Operation can be switched between the remote operat-
Indoor unit
ing panel and local controller.
Operations (e.g., temperature adjustment, airflow, air-
flow direction) except for start/stop operations can be
performed even if operations from the local remote
controller are prohibited.
In the case of simultaneous twin, triple, quad units,
connect the controller to one indoor unit only.
If connected to 2 or more indoor units, an error may
occur.(operation stop)
Control by an external timer is possible by connecting it.
Use of optional "remote ON/OFF adapter" enables
remote control via relay. (Level signal)
Extraction of non-voltage contact output
Use of optional "remote operation adapter" and
Adapter
"remote display panel" (Part to be provided at
Indoor unit
your site) provides non-voltage contact outputs of
signals (operation, error) and operation/stop input
function.
Extraction of DC12 V contact output
Use of optional "Multiple remote controller adapter"
and "remote display panel" (Part to be provided at
your site)provides DC12 V contact outputs of signals
(operation, error) and operation/stop input function.
Features
Parts Required in Addition to Standard System
Components (Indoor/Outdoor Units, Remote Controller)
Wired remote controller (addi-
tional)
(PAR-21MAA)
For PKA type, use remote
controller
(PAR-21MAAT-E)
* For models equipped with a
terminal block.
For PKA type, use remote
controller
(PAR-21MAAT-E)
* For models equipped with a
terminal block.
Remote ON/OFF adapter
(PAC-SE55RA-E)
Relay box
(Part to be provided at your site)
Remote operating panel
(Part to be provided at your site)
Remote ON/OFF adapter
(PAC-SE55RA-E)
Remote operation adapter
(PAC-SF40RM-E)
Remote display panel
(Part to be provided at your site)
Multiple remote controller adapter
(PAC-SA88HA)
Remote display panel
(Part to be provided at your site)

Hide quick links:

Advertisement

Table of Contents
loading