List of Parameters
Param-
Regis-
Name
eter
ter No.
No.
(Hex)
n037
0125
Motor
protection
characteris-
tics
n038
0126
Motor pro-
tective time
3-10
Description
Used to set the motor overload
detection (OL1) for the electronic
thermal characteristics of the motor.
0: Protection characteristics for
general-purpose induction
motors
1: Protection characteristics for
inverter-dedicated motors
2: No protection
Note If a single Inverter is con-
nected to more than one
motor, set the parameter to 2
for no protection. The param-
eter is also disabled by set-
ting n036 for rated motor to
0.0.
Used to set the electric thermal
characteristics of the motor to be
connected in 1-minute increments.
Note The default setting does not
require any changes in nor-
mal operation.
Note To set the parameter accord-
ing to the characteristics of
the motor, check with the
motor manufacturer the ther-
mal time constant and set
the parameter with some
margin. In other words, set
the value slightly shorter
than the thermal time con-
stant.
Note To detect motor overloading
quicker, reduce the set
value, provided that it does
not cause any application
problems.
Chapter 3
Setting
Default
Chan-
range
setting
ges
during
opera-
tion
0 to 2
0
No
1 to 60
8
No
Memo