Omron SYSDRIVE 3G3MV Setup Manual page 92

Sysdrive 3g3mv series multi-function compact inverter
Hide thumbs Also See for SYSDRIVE 3G3MV:
Table of Contents

Advertisement

List of Parameters
Param-
Regis-
Name
eter
ter No.
No.
(Hex)
n169
01A9
Output open-
phase detec-
tion time
(See note 1.)
n170
---
Enter com-
mand (Save
to EEPROM)
receive
condition
(DeviceNet
and
RS-422A/485
communica-
tions)
n171
---
Not used
to
n174
n175
01AF
Low-speed
carrier fre-
quency re-
duction
selection
Note 1. Available for 5.5-kW and 7.5-kW Inverters only.
Note 2. The default setting for 5.5-kW and 7.5-kW Inverters is "1."
3-38
Description
Sets the output open-phase detec-
tion time in units of seconds.
If "0" is set, the output open-phase
detection function will be disabled.
Recommended setting: 0.2 (s)
0: Disable Enter command reception
during operations
1: Always enable Enter command
reception
---
This function automatically reduces
the carrier frequency to 2.5 kHz if
the output frequency is 5 kHz or
less, and the output current is 110%
or greater than the rated Inverter
current. Normally this setting is not
necessary. This function improves
the overload capacity at low fre-
quencies.
0: Disables low-speed carrier fre-
quency reduction.
1: Enables low-speed carrier fre-
quency reduction.
Note Normally, it is not necessary
to change the default setting.
Note This function is enabled if
n080 (carrier frequency) is set
to 2, 3, or 4.
Chapter 3
Set-
Default
Chan-
ting
setting
ges
range
during
opera-
tion
0.0 to
0.0
No
2.0
0, 1
0
No
---
---
---
0, 1
0 (See
No
note 2.)
Memo