Mitsubishi Heavy Industries FDTCVA SERIES Technical Manual page 56

Packaged/multi-type (v-multi)packaged air-conditioner
Table of Contents

Advertisement

(c) Triple type
Model FDENVA602HEN T2R (Indoor unit: 3 units, Outdoor unit: 1 unit)
Item
(1)
Nominal cooling capacity
Nominal heating capacity
(1)
Power source
Cooling power consumption
Running current (Cooling)
Power factor (Cooling)
Heating power consumption
Running current (Heating)
Power factor (Heating)
Inrush current (L.R.A)
Noise level
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q'ty
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
Defrost control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air fl ow
Outside air intake
Air filter, Q'ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Notes (1) The data are measured at the following conditions.
Operation
Cooling
Heating
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 "UNITARY AIR-CONDITIONERS"
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
(4) Values in [ ~
(5) Indoor unit specifications show the specifications for one unit. Capacity and running characteristics values are shown for the case where three indoor
units are combined and run together.
(6) If wireless specifications are used, use 1 wireless indoor unit in combination with wired indoor units.
Model
kW
kW
kW
A
%
kW
A
%
A
dB(A)
mm
kg
kg
r
W
CMM
W
Wireless remote control switch (Optional: RCN-E1R)
Wired remote control switch (Optional: RC-E1R)
Liquid line
mm
(in)
Gas line
Connectable with VP20 (I.D. 20mm, O.D. 26mm)
Indoor air temperature
Item
DB
27˚C
20˚C
] show the minimum to maximum range.
FDENVA602HENT2R
FDENA201R
1 Phase, 220-240V 50Hz/220V 60Hz
Powerful mode Hi:42 Me:39 Lo:38
Mild mode Hi:39 Me:38 Lo:37
210 × 1070 × 690
30
Louver fin & inner grooved tubing
Microcomputer controlled de-icer
Multiblade centrifugal fan × 2
30 × 1
Direct line start
Powerful mode Hi:12 Me:11 Lo:9
Mild mode Hi:11 Me:9 Lo:7
Unavailable
Plastic net (washable) × 2
Rubber sleeve (for fan motor)
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat.
Indoor branch pipe, Outdoor main pipe: φ9.52(3/8")
Indoor branch pipe:φ12.7 (1/2"), Outdoor main pipe: φ15.88 (5/8")
Necessary (both Liquid & Gas lines)
Mounting kit. Drain hose
WB
DB
19˚C
35˚C
7˚C
55
-
-
FDCVA602HENAR
14.0 [6.7~14.5]
16.0 [6.3~16.5]
4.85/4.85
21.2/22.2
99/99
4.58/4.58
20.2/21.1
99/99
5
53
845 × 970 × 370
74
RM-B5125MDE21 × 1
Direct line start
Straight fin & inner grooved tubing
Electronic expansion valve
R410A
3.8 [Pre-charged up to the piping length of 30m]
0.7 (M-MA68)
Propeller fan × 1
120 × 1
Direct line start
Cooling: 75, Heating: 73
Rubber mount (for compressor)
20 (Crank case heater)
– (Indoor unit side)
Internal thermostat for fan motor.
Anomalous discharge temperature protection.
Flare piping
Outdoor air temperature
WB
24˚C
6˚C
Standards
ISO-T1