Model FDTVA1002HESD2R (Indoor unit: 4 units, Outdoor unit: 1 unit)
Item
(1)
Nominal cooling capacity
Nominal heating capacity
(1)
Power source
Cooling power consumption
Running current (Cooling)
Power factor (Cooling)
Heating power consumption
Running current (Heating)
Power factor (Heating)
Inrush current (L.R.A)
Noise level
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q'ty
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
Defrost control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air fl ow
Outside air intake
Air filter, Q'ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
Liquid line
Installation data
Refrigerant piping size
Gas line
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Notes (1) The data are measured at the following conditions.
Operation
Cooling
Heating
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 "UNITARY AIR-CONDITIONERS"
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
(5) Indoor unit specifications show the specifications for one unit. Capacity and running characteristics values are shown for the case where four indoor
units are combined and run together.
(6) Be sure to use the accessory pipe to connect service valve on the gas side with the fi eld pipe.(Refer to the 220 page).
Model
kW
kW
kW
A
%
kW
A
%
A
Powerful mode Hi:38 Me:35 Lo:33
dB(A)
Mild mode Hi:35 Me:33 Lo:31
mm
kg
Louver fin & inner grooved tubing
kg
r
W
Powerful mode Hi:20 Me:17 Lo:15
CMM
Mild mode Hi:17 Me:15 Lo:13
W
Wired remote control switch (Optional : RC-E1R)
Wireless kit (Optional : RCN-T-35W-ER)
Internal thermostat for fan motor.
mm
(in)
(6)
Connectable with VP25 (I.D. 25mm, O.D. 32mm)
Mounting kit. Drain hose, Reducer kit, (Please see page 218), Accessory pipe (Please see page 220)
Indoor air temperature
Item
DB
27˚C
20˚C
FDTVA1002HESD2R
FDTA251R
25.0 [10.6~28.0]
28.0 [9.5~31.5]
3 Phase, 380-415V 50Hz/380V 60Hz
Unit 270 × 840 × 840
Panel 35 × 950 × 950
31 (Unit:24 Panel:7)
Microcomputer controlled de-icer
Turbo fan × 1
20 × 1
Direct line start
Available
Plastic net (washable) × 1
Rubber sleeve (for fan motor)
Thermostat by electronics
Frost protection thermostat.
Indoor branch pipe: φ9.52 (3/8"), Outdoor main pipe: φ12.7 (1/2")
Indoor branch pipe: φ15.88 (5/8"), Outdoor main pipe: φ25.4 (1")
Flare piping (Outdoor gas piping: Brazing)
Necessary (both Liquid & Gas lines)
Decorative Panel (T-PSA-35W-ER)
Outdoor air temperature
WB
DB
19˚C
35˚C
7˚C
35
-
-
FDCVA1002HESAR
8.86/8.90
13.3/14.3
96/95
8.43/8.47
12.9/13.9
94/93
5
Cooling:57, Heating: 58
1505 × 970 × 370
140
GT-C5150ND79 × 1
Direct line start
Straight fin & inner grooved tubing
Electronic expansion valve
R410A
7.2 [Pre-charged up to the piping length of 30m]
1.45 (M-MA32R)
Propeller fan × 2
120 × 2
Direct line start
Cooling: 150, Heating: 145
Rubber mount (for compressor)
20 (Crank case heater)
– (Indoor unit side)
Internal thermostat for fan motor.
Anomalous discharge temperature protection.
WB
24˚C
6˚C
Standards