Mitsubishi Heavy Industries FDTCVA SERIES Technical Manual page 247

Packaged/multi-type (v-multi)packaged air-conditioner
Table of Contents

Advertisement

Model: FDUM, FDU series
CNT
Drain motor
52X3
CNW1
PCB power supply connector
(Primary side)
SETTING BY THE JUMPER WIRE
±
Name
Closed
Input signal for CnT - Level input
J1 (SW7-1)
(1)
Open
Input signal for CnT - Pulse input
Closed
Heating thermostat OFF-Lo Fan speed
J2 (SW7-2)
(1)
Open
Heating thermostat OFF-Stop for 5 min then Lo fan speed
Closed
Input signal for CnT - Normal operation (Run/Stop)
J3 (SW7-3)
(1)
Open
Input signal for CnT - Operation permission/prohibition
Closed
Normal
J4 (SW7-4)
(1)
Open
Set point for Heating offset by +3˚C
Closed
Freeze prevention fan control activated
J6 (SW8-2)
(1)
Open
Freeze prevention fan control deactivated
Note (1)
"Open" means that jumper wire is not provided on the PCB or the
connection is cut.
(2)
The replacement PCB is not equipped with jumpers J1 ~ J4, J6. Instead,
SW7 and 8, with the same functions as jumpers J1~J4, J6, are used in
the position where the jumpers were previously. Set SW7 and 8 locally
in accordance with the above table.
Heat exchanger thermistor,
Return air thermistor
(Thl-R1, Thl-A)
Heat exchanger thermistor
(Thl-R2)
Connector
(CNT)
CNN1 CNN2
CNH
CNV
CNO
52X2
52X1
52X6
F1
CNM3
CNW0
Function
Address swith
(SW2)
DIP switch
(SW5)
Remote controller
J10~J11
(SW10)
CNB
CNQ
CNF
SW2
SW10
SW5
LED2
LED1
CNE
CNG
CNW2
PCB power supply connector
Power supply
(Secondary side)
CONTROL SETTING SWITCH (SW5, SW9, SW10)
±
Function of DIP switch SW5 Master/slave setting and fi lter
sign setting (Usually all turned OFF)
Switch
ON
SW5-1
OFF
ON
SW5-3
OFF
Function of DIP switch SW9
Switch
SW9-3
SW9-4
Function of DIP switch SW10
Switch
OFF
SW10-2
(J10)
ON
246
-
-
J6
(SW8)
DIP switch
(SW9)
J1~J4
(SW7)
CNZ
CNI
SW8
SW9
SW7
CNK1
CNK2
Function
ON
Slave c
OFF
Slave b
SW5-2
ON
Slave a
OFF
Master
Setting time : 1000hrs. (Unit stop)
ON
OFF
Setting time : 1000hrs. (Display)
SW5-4
ON
Setting time : 600hrs. (Display)
OFF
Setting time : 180hrs. (Display factory setting)
Function
Emergency operation
ON
Normal
OFF
Fan control : High speed (High Ceiling)
ON
Fan control : Standard
OFF
Function
OFF
Remote controller air flow –
ON
Remote controller air flow 1 speed
SW10-3
OFF
Remote controller air flow 2 speed
(J11)
ON
Remote controller air flow 3 speed
Float switch