Mitsubishi Heavy Industries FDTCVA SERIES Technical Manual page 216

Packaged/multi-type (v-multi)packaged air-conditioner
Table of Contents

Advertisement

1) Place the unit outlet pipe perpendicular to the wind direction.
2) Please install so the direction of the air from the blowing outlet will be perpendicular to the direction of the wind.
3) When the foundation is not level, use wires to tie down the unit.
(d) Installation space
Walls surrounding the unit in the four sides are not acceptable.
±
There must be a 1-meter or larger space in the above.
±
Where a danger of short-circuting exists, install guide louvers.
±
±
When more than one unit are installed, provide suffi cient intake space consciously so that short-circuiting may not oc-
cur.
Where pilling snow can bury the outdoor unit, provide proper snow guards.
±
Installation
example
Distance
Open
L1
space
L2
L3
L4
(e) Installation
Anchor bolt fixed position
A
Notabilia for installation
Fasten with bolts
Use a long block to
extend the width.
(f)
To run the unit for a cooling operation,when the outdoor temperature is -5˚C or lower. Please equip a fl ex
fl ow adapter and a snow guard hood (option) on the unit.
Wind direction
Fasten with anchor bolts
FDCVA151~251
I
II
III
I
Open
280
280
space
Open
100
75
300
space
100
80
80
100
Open
250
250
250
space
Unit: mm
Air inlet
Air outlet
D
B
(M10-12)
Use a thicker block to
anchor deeper.
FDCVA302
FDCVA402~100z
II
III
I
Open
Open
Open
500
space
space
space
Open
250
300
space
150
100
150
250
250
5
Item
A
Model
FDCVA151~251
106
FDCVA302
150
FDCVA402~1002
190
In installing the unit, fi x the unit's legs with bolts specifi ed on the
±
left.
The protrusion of an anchor bolt on the front side must be kept within
±
15 mm.
Securely install the unit so that it does not fall over during earthquakes
±
or strong winds, etc.
Refer to the left illustrations for information regarding concrete
±
foundations.
Install the unit in a level area. (With a gradient of 5 mm or less.)
±
Improper installation can result in a compressor failure, broken piping
±
within the unit and abnormal noise generation.
215
-
-
Over 500 mm
Wind direction
Wind direction
Fasten with anchor bolts
Unit: mm
Air inlet
II
III
L
2
500
Air
Open
inlet
5
space
Air outlet
300
150
5
5
B
C
D
164
312.5
510
150
380
580
200
410
580
Wind direction
L
3
L
4
service
space
L
1
Unit: mm
E
F
14
13.5
19
19
20
20