SST (F)
70
TC
173.2
20
kW
13.4
TC
192.1
25
kW
13.6
TC
212.2
30
kW
13.8
TC
233.4
35
kW
14.0
TC
255.6
40
kW
14.2
TC
278.5
45
kW
14.4
TC
301.7
50
kW
14.7
SST (F)
70
TC
194.9
20
kW
15.2
TC
215.3
25
kW
15.7
TC
236.9
30
kW
16.2
TC
259.6
35
kW
16.7
TC
283.2
40
kW
17.2
TC
306.7
45
kW
17.8
TC
331.0
50
kW
18.4
LEGEND
kW
— Compressor Power
SST
— Saturated Suction Temperature Entering Condensing Unit
TC
— Gross Cooling Capacity (1000 Btuh)
NOTES:
1. Ratings are based on 15 F superheat and use of R-410A
refrigerant.
2. Ratings include suction line losses due to an accumulator
3. Refer to Commercial Split Builder program for more detailed
information.
38APD050 CONDENSING UNIT CIRCUIT RATINGS, 50 Hz ENGLISH
CONDENSER ENTERING-AIR TEMPERATURE (F)
80
85
162.5
157.0
151.4
15.0
15.9
180.4
174.6
168.6
15.2
16.1
199.8
193.2
186.8
15.5
16.3
219.9
212.9
205.8
15.7
16.6
240.9
233.2
225.5
15.9
16.8
262.3
253.8
245.5
16.1
17.0
284.1
274.6
266.1
16.3
17.2
CONDENSER ENTERING-AIR TEMPERATURE (F)
80
85
183.8
178.3
172.6
16.9
17.8
203.2
197.1
190.9
17.3
18.2
223.7
216.8
210.2
17.8
18.7
245.0
237.5
230.1
18.3
19.2
267.1
258.7
250.5
18.8
19.7
289.5
280.1
271.3
19.4
20.3
311.5
301.9
292.6
20.0
20.9
CIRCUIT A
90
95
100
145.5
139.9
16.8
17.7
18.6
162.5
156.1
17.0
18.0
18.9
180.2
173.5
17.3
18.2
19.2
198.6
191.5
17.5
18.5
19.5
217.9
210.1
17.7
18.7
19.8
237.0
228.9
18.0
19.0
20.0
256.9
247.8
18.2
19.2
20.2
CIRCUIT B
90
95
100
166.9
161.1
18.7
19.7
20.7
184.7
178.1
19.2
20.1
21.2
203.3
196.4
19.6
20.6
21.7
222.4
215.1
20.1
21.1
22.2
242.6
234.2
20.7
21.7
22.7
262.2
253.4
21.2
22.2
23.2
282.4
272.4
21.8
22.8
23.8
105
110
115
133.8
127.9
121.6
19.6
20.6
21.5
149.9
143.5
136.9
19.9
21.0
22.0
166.6
159.5
152.3
20.3
21.3
22.4
184.1
176.7
169.1
20.6
21.6
22.7
202.2
194.2
186.0
20.8
21.9
23.0
220.3
211.6
202.0
21.1
22.2
23.3
238.5
228.2
218.5
21.3
22.4
23.5
105
110
115
155.1
149.2
143.2
21.8
22.9
24.1
171.8
165.1
158.8
22.3
23.4
24.6
189.4
182.0
174.6
22.7
23.9
25.0
207.4
199.6
191.6
23.2
24.4
25.5
225.6
217.0
208.1
23.8
24.9
26.0
243.8
234.0
224.9
24.3
25.4
26.5
261.6
252.0
240.5
24.8
25.9
27.1
120
125
115.2
110.2
22.5
23.6
130.2
123.0
23.1
24.1
145.2
137.8
23.5
24.6
160.9
153.4
23.8
25.0
176.9
168.2
24.2
25.3
192.8
183.9
24.4
25.6
209.4
199.1
24.7
25.9
120
125
137.1
131.0
25.3
26.6
151.9
145.0
25.8
27.0
167.5
159.5
26.3
27.5
183.2
175.0
26.7
28.0
198.6
189.3
27.2
28.4
214.4
204.1
27.7
28.9
229.7
220.0
28.2
29.5
61